SMA POWER PLANT CONTROLLER User Manual
Page 32
7 Operation
SMA Solar Technology AG
32
PPC-BE-P7-en-13
Operating Manual
Figure 14: User interface: Device table - network analyzers (example)
Procedure:
1. Log into the user interface as an installer (see Section 11.3.1, page 54).
2. Go to PPC > Grid system services > Device table Power Analyzers > Power Analyzer 1.
3. If you need to disable network analyzer 1, adjust the setting in the Active column to FALSE.
4. If you need to enable network analyzer 1, adjust the setting in the Active column to TRUE.
5. To change the device type of the network analyzer, click the corresponding button next to the field Type and select
the appropriate device from the device list.
6. To assign a name to a device, enter the desired device name in the field Device name.
7. To change the IP address of a network analyzer, change the IP address of the respective network analyzer in the
corresponding fields.
8. To scale the instantaneous values of voltage, electric current or power, adjust the settings in the associated fields.
9. To scale the input signals on the page PPC > Settings > Modbus server > Standard, in the drop-down list
Customized scaling, select the entry Yes. If No is selected, individual scaling of the measured values P, Q, U and
f is not possible.
10. To adjust the settings for the other network analyzers, go to PPC > Grid system services > Device table Power
Analyzers > Power Analyzer 2 or PPC > Grid system services > Device table Power Analyzers > Power
Analyzer 3.