beautypg.com

10 local specification of setpoints – SMA POWER PLANT CONTROLLER User Manual

Page 37

background image

SMA Solar Technology AG

7  Operation

Operating Manual

PPC-BE-P7-en-13

37

7.10 Local Specification of Setpoints

Control of the system by the Power Plant Controller is normally executed remotely via Modbus commands.
In addition, it is possible for the grid operator to specify fixed setpoints so that remote control of the system is not

necessary. In this case, the system control must be adjusted to Local.
If errors occur during transmission of grid management specifications via Modbus protocol, for diagnostic purposes the

system can be controlled directly from the user interface. To enable settings to be made via the user interface, the system

control needs to be adjusted to Local. After completion of the diagnostic work, reset system control to Remote.

Procedure:

1. Log into the user interface as an installer (see Section 11.3.1, page 54).
2. Go to PPC > Grid system services > Setpoint specification.
3. In the drop-down list System control, select the entry Local.
4. Enter the required values in the fields Active power, Reactive power, Voltage, Power factor and TanPhi.

7.11 Saving and Restoring Settings of the Power Plant Controller

Backing Up Settings

All settings of the Power Plant Controller can be backed up automatically and manually.

Procedure:

1. Log into the user interface (see Section 11.3.1, page 54).
2. Go to PPC > Backup and restore.
3. To export the settings to a USB memory stick, proceed as follows:

• Select the required USB port in the field Port.
• Select the button [Backup] in the field Ini files.

4. To save separate settings in an internal file on the Power Plant Controller, click the button [Export] of the respective

group.

5. To save all settings in an internal file on the Power Plant Controller, click the button [Export] of the group All.

Settings backup Description
Automatic

All Power Plant Controller settings are saved daily at midnight to the SD memory card in the

Power Plant Controller. This data is always saved alternately in the files AutoSave 1 and

AutoSave 2. This means that, in the event of an error, the records from two different days can be

retrieved. You can recognize which of the two files is the more recent by the date on the user

interface.

Manual

It is possible to save all settings to a USB memory stick in one folder

PPC_Backup_xxxxxxxx(serial number). The folder name includes the serial number of the

Power Plant Controller. The Power Plant Controller automatically creates this folder. During

backup, the automatically saved files AutoSave 1 and AutoSave 2 are also transferred to the

USB memory stick.
In addition, all settings, or the settings of all inverters, Cluster Controllers, controllers and IP

addresses, can be saved separately in an internal file of the Power Plant Controller.