SMA POWER PLANT CONTROLLER User Manual

Page 29

background image

SMA Solar Technology AG

7  Operation

Operating Manual

PPC-BE-P7-en-13

29

7.6.2 Adjusting the Configuration of the Sunny Centrals

After commissioning the Power Plant Controller, you can still change the IP address of individual Sunny Centrals, assign

a unique name to Sunny Centrals or disable the setpoint specified by the Power Plant Controller for individual

Sunny Centrals.

Figure 13: User interface: Device table inverters (example)

Procedure:

1. Log into the user interface as an installer (see Section 11.3.1, page 54).
2. Go to PPC > Grid system services > Device table inverters.
3. Adjust the desired settings for the Sunny Centrals as follows:

– enter a unique name for the inverter in the field Device name
– deactivate the setpoint specified by the Power Plant Controller in the Active column (adjust setting to FALSE) or

activate (adjust setting to TRUE)

– change the IP address, port and UID of the inverter
– in the field Read profile, change the profile of the Modbus protocol with which the measured values are

transmitted by the Sunny Central.

Profile

Explanation

0

The standard SMA Modbus protocol is used.

1

The Power Plant Controller Modbus profile is used. This option is applicable for future use.