11.1.4 Updating the Firmware via the User Interface of the

Sunny WebBox

You need an SD card. If other update files are already stored on the SD card, these will be deleted.

1. Ensure that an SD card is inserted into the Sunny WebBox SD card slot.
2. Log into the Sunny WebBox as an installer.
3. Select the required update file in the downloads area at www.SMA-Solar.com and download

it to your computer.

4. Click the [Browse...] button under "WebBox > Info" in the "Manual update" field in the user

interface.

5. Select the desired update file and click [Open].
6. Click [Upload] in the "Manual Update" field.

☑ The Sunny WebBox uploads the file and saves it to the inserted SD card. The Sunny WebBox

then restarts automatically and installs the firmware update. If the firmware update was
successful, you can find the new firmware version under "WebBox > Info" in the
"Version Firmware" field.

11.2 Performing a Firmware Update for the Inverters

From firmware version 1.53f12 and firmware profile 1.43, the Sunny WebBox can transmit firmware
updates to the inverters in the system. The following inverters are able to receive firmware updates
from the Sunny WebBox.

• Sunny Tripower (STP) inverters from firmware version 2.33
• Sunny Boy (SB) inverters:

– SB xxxxTL-20 from inverter firmware version 3.10.x.x.R

To perform the firmware update, an SD memory card is required.

1. Select the required update files in the download area of the inverter at www.SMA-Solar.com

and download it to your computer.

2. Connect the SD memory card to the computer and create a folder named "bu" on the SD

memory card.

3. Copy the downloaded update files to the "bu" folder created on the SD memory card and then

remove the SD memory card from the computer.

NOTICE!
Transfer of grid operator setpoints via RS485 not possible during firmware
update
During the firmware update, the Sunny WebBox does not send grid operator setpoints via
RS485 to inverters in the system. Thus, the grid operator cannot control the system.

• If you want to perform the firmware update during feed-in operation during the day,

contact your grid operator in advance, if necessary.