Grounding the switch – H3C Technologies H3C S12500 Series Switches User Manual

Page 35

background image

25

Figure 21 Installing L-shaped brackets

(1) Anchor bolt

(2) L-shaped bracket

Grounding the switch

WARNING!

For the safety of operators and equipment, securely ground the switch. Make sure the resistance reading
between the switch chassis and the ground is less than 1 ohm.

Most racks are equipped with a grounding strip. You can connect the yellow-green grounding cable of

the switch to the grounding strip.

CAUTION:

Connect the grounding cable to the earthing system in the equipment room. Do not connect it to a fire main
or lightning rod.

Use the supplied grounding cable (CAT 6 cable with dual-hole ring terminals).
To connect the grounding cable:

1.

Remove the two grounding screws from the switch chassis.

2.

Use the grounding screws to attach one end of the grounding cable to the chassis.

3.

Connect the other end of the grounding cable to the grounding strip of the rack in the same way.