CHAPTER 1 CLICK 340/341/342 MANAGED SWITCHES

3 Swivel the bottom of the module away from the DIN rail slightly (A).

4 Lift the module upwards away from the DIN rail (B).

Figure 1.5 – Removing the Switch

Wiring the Managed Switch

The Click 340/341/342 is operated with a 24 VDC voltage that can be supplied redundantly,

if required (see Figure 1.6). Use the table and figure below to wire the supply voltage.

Terminal

Meaning

1

Supply voltage +US1

2

GND US1

3

Supply voltage +US2

4

GND US2

5 and 6

Floating alarm contact

7

Functional earth ground

(optional)

8

Not used

Table 1.2 – Assignment of the Pluggable Screw Terminal

Note

If redundant power supply monitoring is active (default setting), an error is indicated
if only one voltage is applied. A bridge between US1 and US2 prevents this error mes-
sage. It is also possible to deactivate monitoring in Web-based management (see
Chapter 4).