English-8, Power alarm – Delta Electronics AC Drive VFD-F Series User Manual

Page 8

background image

English-8

20 HP to 40 HP (VFD150F23A, VFD185F23A/43A, VFD220F23A/43A, VFD300F43A)

W/T3

V/T2

3

IM

POWER

S/L2

R/L1

-

( )

( )

+

DC DC

T/L3 +1

-

+2

MOTOR


50 HP to 60 HP (VFD370F43A, VFD450F43A)

R/L1

+1

+2

-

S/L2 T/L3

U/T1 V/T2 2/T3

POWER

IM

MOTOR

3

POWER

ALARM

CHARGE

Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG

Power Terminal
Torque: 30Kgf-cm (26 in-lbf)
Wire: 8-2 AWG
Wire Type: Stranded copper only, 75° C
NOTE: If wiring of the terminal utilizes the wire
with a 1AWG-diameter, it is thus necessary to use
the Recognized Ring Terminal to conduct a
proper wiring.

Control Terminal
Torque: 4Kgf-cm (3 in-lbf)
Wire: 12-24 AWG

Power Terminal
Torque: 57kgf-cm (49.5 in-lbf) min.
Wire Gauge: VFD370F43A: 3AWG

VFD450F43A: 2AWG

Wire Type: Stranded copper only, 75° C