Delta Electronics AC Drive VFD-F Series User Manual
Page 26
English-26
Parameter
Functions
Settings
Factory
Setting
Customer
11-06 Motor
Switch
Frequency
during Fixed Amount
Circulation
0.00 to 120.00 Hz
60.00
11-07
Enter Sleep Process
Time
0.0~3600.0sec
0.0: Sleep function disable
0.0
11-08
Sleep Frequency of
Sleep Process
0.00 to 11-09 (Wake up Frequency)
0.0
11-09
Wake Up Frequency of
Sleep Process
0.00 to 120.0Hz
0.0
11-10
Treatment of Fixed
Amount Circulation
Malfunction
00: Turn off all motors
01: Turn off AC drive
00
11-11
Stop Frequency of
Auxiliary Motor
0.00~120.00Hz 0.00
Fault Codes
Fault
Name
Fault Descriptions
Corrective Actions
Software
protection failure
Return to the factory.
GFF hardware
error
Return to the factory.
CC (Current
Clamp)
Return to the factory.
OC hardware error
Return to the factory.
OV hardware error
Return to the factory.
OH hardware error
Return to the factory.
Over current
Abnormal increase
in current.
1. Check whether the motors horsepower corresponds to the
AC drive output power.
2. Check the wiring connections between the AC drive and
motor for possible short circuits.
3. Increase the Acceleration time.
4. Check for possible excessive loading conditions at the motor.
5. If there are any abnormal conditions when operating the AC
drive after short-circuit being removed, it should be sent back
to manufacturer.
Over voltage
The DC bus voltage
has exceeded its
maximum allowable
value.
1. Check whether the input voltage falls within the rated AC
drive input voltage.
2. Check for possible voltage transients.
3. Bus over-voltage may also be caused by motor regeneration.
Either increase the decel time or add an optional brake
resistor.
4. Check whether the required brake power is within the
specified limits.