Parameter
Functions
Settings
Factory
Setting
Customer
06-03 Over-torque
Detection
Selection
00: Over-torque detection disabled.
01: Over-torque detection enabled during
constant speed operation (OL2), and
operation continues.
02: Over-torque detection enabled during
constant speed operation (OL2), and
operation halted.
03: Over-torque detection enabled during
operation (OL2), and operation
continues.
04: Over-torque detection enabled during
operation (OL2), and operation halted.
00
06-04 Over-torque
Detection
Level
30~150% 110
06-05 Over-torque
Detection
Time
0.1~60.0 Sec
0.1
06-06 Electronic
Thermal
Relay Selection
00: Operate disabled.
01: Operate with a standard motor.
02: Operate with a special motor.
02
06-07 Electronic
Thermal
Characteristic
30~600 Sec
60
06-08
Low Current Detection
Level
00~100% (00 disabled)
00
06-09
Low Current Detection
Time
0.1~ 3600.0 Sec
10.0
06-10
Low Current Detection
Treatment
00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating
01
06-11
Present Fault Record
00
06-12
Second Most Recent
Fault Record
00
06-13
Third Most Recent Fault
Record
00
06-14
Fourth Recent Fault
Record
00: No Fault
01: Oc (over-current)
02: Ov (over-voltage)
03: OH (over temperature)
04: OL (over load)
05: oL1 (over load 1)
06: EF (external fault)
07: Occ (IGBT module is abnormal)
08: cF3 (driver’s internal circuitry
abnormal)
09: HPF (hardware protection failure)
10: OcA (over-current during acceleration)
11: Ocd (over-current during deceleration)
12: Ocn (over-current during steady state
operation)
13: GFF (Ground Fault)
14: Lv (Low voltage)
15: cF1 (EEPROM WRITE failure)
16: cF2 (EEPROM READ failure)
17: bb (Base block)
18: OL2 (over load2)
19: Reserved
20: Code (software/password protection)
21: EF1 (Emergency stop)
22: PHL (phase-loss)
00