Parameter

Functions

Settings

Factory

Setting

Customer

06-03 Over-torque

Detection

Selection

00: Over-torque detection disabled.
01: Over-torque detection enabled during

constant speed operation (OL2), and
operation continues.

02: Over-torque detection enabled during

constant speed operation (OL2), and
operation halted.

03: Over-torque detection enabled during

operation (OL2), and operation
continues.

04: Over-torque detection enabled during

operation (OL2), and operation halted.

00

06-04 Over-torque

Detection

Level

30~150% 110

06-05 Over-torque

Detection

Time

0.1~60.0 Sec

0.1

06-06 Electronic

Thermal

Relay Selection

00: Operate disabled.
01: Operate with a standard motor.
02: Operate with a special motor.

02

06-07 Electronic

Thermal

Characteristic

30~600 Sec

60

06-08

Low Current Detection
Level

00~100% (00 disabled)

00

06-09

Low Current Detection
Time

0.1~ 3600.0 Sec

10.0

06-10

Low Current Detection
Treatment

00: Warn and Ramp to stop
01: Warn and Coast to stop
02: Warn and keep operating

01

06-11

Present Fault Record

00

06-12

Second Most Recent
Fault Record

00

06-13

Third Most Recent Fault
Record

00

06-14

Fourth Recent Fault
Record

00: No Fault
01: Oc (over-current)
02: Ov (over-voltage)
03: OH (over temperature)
04: OL (over load)
05: oL1 (over load 1)
06: EF (external fault)
07: Occ (IGBT module is abnormal)
08: cF3 (driver’s internal circuitry

abnormal)

09: HPF (hardware protection failure)
10: OcA (over-current during acceleration)
11: Ocd (over-current during deceleration)
12: Ocn (over-current during steady state

operation)

13: GFF (Ground Fault)
14: Lv (Low voltage)
15: cF1 (EEPROM WRITE failure)
16: cF2 (EEPROM READ failure)
17: bb (Base block)
18: OL2 (over load2)
19: Reserved
20: Code (software/password protection)
21: EF1 (Emergency stop)
22: PHL (phase-loss)

00