Delta Electronics AC Drive VFD-F Series User Manual

Page 15

background image

English-15

Parameter

Functions

Settings

Factory

Setting

Customer

a01-14 Deceleration Time 3

0.1~3600.0 Sec

10.0/

60.0

a01-15 Acceleration Time 4

0.1~3600.0 Sec

10.0/

60.0

a01-16 Deceleration Time 4

0.1~3600.0 Sec

10.0/

60.0

a01-17 JOG Acceleration Time

0.1~3600.0 Sec

10.0/

60.0

a01-18 JOG Deceleration Time

0.1~3600.0 Sec

10.0/

60.0

a01-19 JOG frequency

0.0 Hz~120.00 Hz

6.00

01-20

S Curve Delay Time in
Accel

0.00~2.50sec 0.00

01-21

S Curve Delay Time in
Decel

0.00~2.50sec 0.00

a01-22 Modulation

Index

0.90~1.20

1.00

01-23

Accel/Decel Time Unit

00: Unit is 1 Sec
01: Unit is 0.1 Sec
02: Unit is 0.01 Sec

01

Group 2 Digital Output/Input Parameter

Parameter

Functions

Settings

Factory

Setting

Customer

a02-00 Source of Frequency

Command

00: via keypad
01: via analog input AVI
02: via analog input ACI1
03: via analog input ACI2
04: via RS485 serial communication
05: via External Reference

00

a02-01 Source of Operation

Command

00: Controlled by the digital keypad
01: Controlled by the external terminals,

keypad STOP enabled.

02: Controlled by external terminals,

keypad STOP disabled.

03: Controlled by the RS-485

communication interface, keypad
STOP enabled.

04: Controlled by the RS-485

communication interface, keypad
STOP disabled.

00

02-02

Stop Method

00:Stop = ramp to stop, E.F. (External

Fault) = coast to stop

01:Stop = coast to stop, E.F. = coast to

stop

02:Stop = ramp to stop, E.F. = ramp to

stop

03:Stop = coast to stop, E.F. = ramp to

stop

00

a02-03 PWM Carrier Frequency

Selections

1~10HP: 4000~10000Hz
15~30HP: 3000~9000Hz
≧40HP: 2000~6000Hz

9000Hz
6000Hz
4000Hz