Delta Electronics AC Drive VFD-F Series User Manual

Page 23

background image

English-23

Parameter

Functions

Settings

Factory

Setting

Customer

08-02

DC Brake Time during
Stopping

0.00~60.00 Sec

0.0

08-03

Start-point for DC Brake 0.00~120.00 Hz

0.00

08-04

Momentary Power Loss
Operation Selection

00: Disable
01: Trace from top downward
02: Trace from bottom upward

00

08-05 Maximum

Allowable

Power Loss Time

0.1~5.0 Sec

2.0

08-06

Speed Search Time

0.1~5.0 Sec

0.5

08-07 Maximum

Speed

Search Current

30~150% 110

08-08 BB

speed

search

method

00: Trace from top downward
01: Trace from bottom upward

00

08-09

Auto Restart Times after
Fault

00~10 00

08-10

Auto Restart Time after
Fault

00 to 60000 sec

600

08-11 Operation

Frequency

Inhibition 1 UP

0.00~120.00 Hz

0.00

08-12 Operation

Frequency

Inhibition 1 DOWN

0.00~120.00 Hz

0.00

08-13 Operation

Frequency

Inhibition 2 UP

0.00~120.00 Hz

0.00

08-14 Operation

Frequency

Inhibition 2 DOWN

0.00~120.00 Hz

0.00

08-15 Operation

Frequency

Inhibition 3 UP

0.00~120.00 Hz

0.00

08-16 Operation

Frequency

Inhibition 3 DOWN

0.00~120.00 Hz

0.00

08-17 Automatic

Energy-

saving

00: Energy-saving operation disabled
01: Energy-saving operation enabled

00

08-18 Automatic

Voltage

Regulation (AVR)

00: AVR function enabled
01: AVR function disabled
02: AVR function disabled for deceleration

00

a08-19 Software Setting of the

Brake Level
(the action level of the
brake resistor)

230V: 370~410VDC
460V: 740~820VDC
00:Disable

380.0
760.0

a08-20 Vibration

Compensation

Factor

00~1000 00

Group 9 Communication Parameters

Parameter

Functions

Settings

Factory

Setting

Customer

a09-00 Communication

Address 01-254

00:Disable

01

a09-01 Transmission

Speed

(Baud Rate)

00: Baud rate 4800
01: Baud rate 9600
02: Baud rate 19200
03: Baud rate 38400

01