Delta Electronics AC Drive VFD-F Series User Manual
Page 23
English-23
Parameter
Functions
Settings
Factory
Setting
Customer
08-02
DC Brake Time during
Stopping
0.00~60.00 Sec
0.0
08-03
Start-point for DC Brake 0.00~120.00 Hz
0.00
08-04
Momentary Power Loss
Operation Selection
00: Disable
01: Trace from top downward
02: Trace from bottom upward
00
08-05 Maximum
Allowable
Power Loss Time
0.1~5.0 Sec
2.0
08-06
Speed Search Time
0.1~5.0 Sec
0.5
08-07 Maximum
Speed
Search Current
30~150% 110
08-08 BB
speed
search
method
00: Trace from top downward
01: Trace from bottom upward
00
08-09
Auto Restart Times after
Fault
00~10 00
08-10
Auto Restart Time after
Fault
00 to 60000 sec
600
08-11 Operation
Frequency
Inhibition 1 UP
0.00~120.00 Hz
0.00
08-12 Operation
Frequency
Inhibition 1 DOWN
0.00~120.00 Hz
0.00
08-13 Operation
Frequency
Inhibition 2 UP
0.00~120.00 Hz
0.00
08-14 Operation
Frequency
Inhibition 2 DOWN
0.00~120.00 Hz
0.00
08-15 Operation
Frequency
Inhibition 3 UP
0.00~120.00 Hz
0.00
08-16 Operation
Frequency
Inhibition 3 DOWN
0.00~120.00 Hz
0.00
08-17 Automatic
Energy-
saving
00: Energy-saving operation disabled
01: Energy-saving operation enabled
00
08-18 Automatic
Voltage
Regulation (AVR)
00: AVR function enabled
01: AVR function disabled
02: AVR function disabled for deceleration
00
a08-19 Software Setting of the
Brake Level
(the action level of the
brake resistor)
230V: 370~410VDC
460V: 740~820VDC
00:Disable
380.0
760.0
a08-20 Vibration
Compensation
Factor
00~1000 00
Group 9 Communication Parameters
Parameter
Functions
Settings
Factory
Setting
Customer
a09-00 Communication
Address 01-254
00:Disable
01
a09-01 Transmission
Speed
(Baud Rate)
00: Baud rate 4800
01: Baud rate 9600
02: Baud rate 19200
03: Baud rate 38400
01