beautypg.com

Delta Electronics AC Drive VFD-F Series User Manual

Page 24

background image

English-24

Parameter

Functions

Settings

Factory

Setting

Customer

a09-02 Transmission

Fault

Treatment

00: Warn and keep operating
01: Warn and RAMP to stop
02: Warn and COAST to stop
03: No warning and no display

03

09-03 Over

Time

Detection

during Transmission

00: Disable
01: Enable

00

09-04

Communication Format 00: 7-bit for ASCII

01: 8-bit for ASCII
02: 8-bit for RTU

00

09-05

Even/Odd Parity and
Stopping Parity Setting

00: None parity + 2 stop bit
01: Even parity + 2 stop bit
02: Odd parity + 2 stop bit
03: None parity + 1 stop bit
04: Even parity + 1 stop bit
05: Odd parity + 1 stop bit

00

a09-06 Communication

Operation Command 1

Bit0~1: 00: Disable

01: Stop
10: Start-up
11: JOG start-up

Bit2~3: Reserved
Bit4~5: 00: No function

01: FWD command
10: REV command
11: Change direction command

Bit6~7: 00: 1

st

step accel/decel speed

01: 2

nd

step accel/decel speed

10: 3

rd

step accel/decel speed

11: 4

th

step accel/decel speed

Bit8~11: 0000: Master speed

0001: 1st step speed
0010: 2nd step speed
0011: 3rd step speed
0100: 4th step speed
0101: 5th step speed
0110: 6th step speed
0111: 7th step speed
1000: 8th step speed
1001: 9th step speed
1010: 10th step speed
1011: 11th step speed
1100: 12th step speed
1101: 13th step speed
1110: 14th step speed
1111: 15th step speed

Bit12: Select Bit6~11 function
Bit13~15 Reserved

00

a09-07 Communication

Frequency Setting

0~120.00Hz 60.00

a09-08 Communication

Operation Command 2

Bit0: 1: EF ON
Bit1: 1: Reset
Bit2: 0: BB OFF, 1: BB ON
Bit3~15: Reserved

00