Parameter
Functions
Settings
Factory
Setting
Customer
a09-02 Transmission
Fault
Treatment
00: Warn and keep operating
01: Warn and RAMP to stop
02: Warn and COAST to stop
03: No warning and no display
03
09-03 Over
Time
Detection
during Transmission
00: Disable
01: Enable
00
09-04
Communication Format 00: 7-bit for ASCII
01: 8-bit for ASCII
02: 8-bit for RTU
00
09-05
Even/Odd Parity and
Stopping Parity Setting
00: None parity + 2 stop bit
01: Even parity + 2 stop bit
02: Odd parity + 2 stop bit
03: None parity + 1 stop bit
04: Even parity + 1 stop bit
05: Odd parity + 1 stop bit
00
a09-06 Communication
Operation Command 1
Bit0~1: 00: Disable
01: Stop
10: Start-up
11: JOG start-up
Bit2~3: Reserved
Bit4~5: 00: No function
01: FWD command
10: REV command
11: Change direction command
Bit6~7: 00: 1
st
step accel/decel speed
01: 2
nd
step accel/decel speed
10: 3
rd
step accel/decel speed
11: 4
th
step accel/decel speed
Bit8~11: 0000: Master speed
0001: 1st step speed
0010: 2nd step speed
0011: 3rd step speed
0100: 4th step speed
0101: 5th step speed
0110: 6th step speed
0111: 7th step speed
1000: 8th step speed
1001: 9th step speed
1010: 10th step speed
1011: 11th step speed
1100: 12th step speed
1101: 13th step speed
1110: 14th step speed
1111: 15th step speed
Bit12: Select Bit6~11 function
Bit13~15 Reserved
00
a09-07 Communication
Frequency Setting
0~120.00Hz 60.00
a09-08 Communication
Operation Command 2
Bit0: 1: EF ON
Bit1: 1: Reset
Bit2: 0: BB OFF, 1: BB ON
Bit3~15: Reserved
00