Group 10 PID Controls
Parameter
Functions
Settings
Factory
Setting
Customer
10-00
Input Terminal for PID
Feedback
00: No function
01: Input via AVI
02: Input via ACI1
03: Input via ACI2
04: Input via External Reference
00
10-01
PID Control Detection
Signal Reference
0.0-6550.0 1000.0
10-02
PID Feedback Control
Method
00: Negative feedback control
01: Positive feedback control
00
10-03
Proportional Gain (P)
0.0~10.0
1.0
10-04
Integral Time (I)
0.00~100.00 Sec
1.00
10-05
Differential Time (D)
0.00~1.00 Sec
0.00
10-06 Upper
Bound
for
Integral Control
00~200% 100
10-07
Primary Low Pass Filter
Time
0.0~2.5 Sec
0.0
10-08 PID
Feedback
Signal
Range
0.0~6550.0 600.0
10-09 PID
Feedback
Signal
Fault Treatment Time
0. 0~3600.0 Sec
0.0: Disable
0.0
a10-10 PID
Feedback
Signal
Fault Treatment
00: Warn and RAMP stop
01: Warn and COAST stop
02: Warn and keep operating
01
a10-11 PID Minimum Output
Frequency
0: By PID controller
1: By AC drive
01
Group 11 Fan and Pump Control Parameters
Parameter
Functions
Settings
Factory
Setting
Customer
11-00
V/f Curve Selection
00: Determined by group 01
01: 1.5 power curve
02: 1.7 power curve
03: 2 power curve
04: 3 power curve
00
11-01
Circulative Control
00: No function
01: Time circulation (by time)
02: Fixed amount circulation (by PID)
03: Fixed amount control (an AC drive
runs with 4 motors)
00
11-02
Multiple Motors Control
01~04
01
11-03
Time Circulation Time
Setting
00~65500 Min
00
11-04 Motor
Switch
Delay
Time
0.0~3600.0 sec
1.0
11-05 Motor
Switch
Delay
Time during Fixed
Amount Circulation
0.0~3600.0 sec
10.0