Delta Electronics AC Drive VFD-F Series User Manual
Page 17
English-17
Parameter
Functions
Settings
Factory
Setting
Customer
03-05 Multi-function
Output
terminal 6
00
03-06 Multi-function
Output
terminal 7
00
03-07 Multi-function
Output
terminal 8
10: Auxiliary 2 output
11: Auxiliary 3 output
12: Auxiliary 4 output
13: Auxiliary 5 output
14: Auxiliary 6 output
15: Auxiliary 7 output
16: Indication during operation
17: Master frequency attained
18: Zero Speed (including shutdown)
19: Over-torque
20: External Fault
21: Low voltage detection
22: Operation Mode indication
23: Fault indication
24: Master Frequency Attained 1
25: Master Frequency Attained 2
26: Over Temperature indication
27: Drive Ready
28: External Emergency Stop (EF1)
29: Software Brake Output
30: OL or OL1 Overload Warning
31: Dwell Indication (sleep)
32: Low Current Indication
33: PID Feedback Error Indication
34: PLC Program Running
35: PLC Program Step Completed
36: PLC Program Completed
37: PLC Program Operation Paused
00
03-08 Master
Frequency
Attained 1
0.00~120.00 Hz
0.00
03-09 Master
Frequency
Attained 2
0.00~120.00 Hz
0.00
03-10 Analog
Output
1,
(AFM1) 0~10Vdc
00
03-11 Analog
Output
2,
(AFM2) 0/4~ 20mA
00: Output frequency
01: Output current
02: Output voltage
03: Frequency command
04: Power factor loading
01
a03-12 Analog Output Gain 1
01~200%
100
a03-13 Analog Output Gain 2
01~200%
100
03-14 Analog
Output
2
Selection (AFM2
Definition)
00: 0~20mA
01: 4~20mA
01
03-15
DC Fan Control
00: Fan runs on power up.
01: Fan begins upon a RUN command.
Fan stops 1 minute after a STOP
command.
02: Fan begins upon a RUN command.
Fan stops after a STOP command
03: Fan is controlled by temperature.
Approximately a 60°C temperature will
start the fan.
00