Parameter

Functions

Settings

Factory

Setting

Customer

03-05 Multi-function

Output

terminal 6

00

03-06 Multi-function

Output

terminal 7

00

03-07 Multi-function

Output

terminal 8

10: Auxiliary 2 output
11: Auxiliary 3 output
12: Auxiliary 4 output
13: Auxiliary 5 output
14: Auxiliary 6 output
15: Auxiliary 7 output
16: Indication during operation
17: Master frequency attained
18: Zero Speed (including shutdown)
19: Over-torque
20: External Fault
21: Low voltage detection
22: Operation Mode indication
23: Fault indication
24: Master Frequency Attained 1
25: Master Frequency Attained 2
26: Over Temperature indication
27: Drive Ready
28: External Emergency Stop (EF1)
29: Software Brake Output
30: OL or OL1 Overload Warning
31: Dwell Indication (sleep)
32: Low Current Indication
33: PID Feedback Error Indication
34: PLC Program Running
35: PLC Program Step Completed
36: PLC Program Completed
37: PLC Program Operation Paused

00

03-08 Master

Frequency

Attained 1

0.00~120.00 Hz

0.00

03-09 Master

Frequency

Attained 2

0.00~120.00 Hz

0.00

03-10 Analog

Output

1,

(AFM1) 0~10Vdc

00

03-11 Analog

Output

2,

(AFM2) 0/4~ 20mA

00: Output frequency
01: Output current
02: Output voltage
03: Frequency command
04: Power factor loading

01

a03-12 Analog Output Gain 1

01~200%

100

a03-13 Analog Output Gain 2

01~200%

100

03-14 Analog

Output

2

Selection (AFM2
Definition)

00: 0~20mA
01: 4~20mA

01

03-15

DC Fan Control

00: Fan runs on power up.
01: Fan begins upon a RUN command.

Fan stops 1 minute after a STOP
command.

02: Fan begins upon a RUN command.

Fan stops after a STOP command

03: Fan is controlled by temperature.

Approximately a 60°C temperature will
start the fan.

00