Delta Electronics AC Drive VFD-F Series User Manual
Page 20
English-20
Parameter
Functions
Settings
Factory
Setting
Customer
a05-14 15
th
Step Speed
Frequency
0.00~120.00 Hz
0.00
05-15
PLC Mode
00: Disable PLC Operation
01: Execute one program cycle
02: Continuously execute program cycles
03: Execute one program cycle step by
step
04: Continuously execute program cycles
step by step
00
05-16
PLC Forward/ Reverse
Motion
00 to 32767 (00: FWD 01: REV)
00
05-17
Time Duration Step 1
0.0 to 65500 sec
0.0
05-18
Time Duration Step 2
0.0 to 65500 sec
0.0
05-19
Time Duration Step 3
0.0 to 65500 sec
0.0
05-20
Time Duration Step 4
0.0 to 65500 sec
0.0
05-21
Time Duration Step 5
0.0 to 65500 sec
0.0
05-22
Time Duration Step 6
0.0 to 65500 sec
0.0
05-23
Time Duration Step 7
0.0 to 65500 sec
0.0
05-24
Time Duration Step 8
0.0 to 65500 Sec
0.0
05-25
Time Duration Step 9
0.0 to 65500 Sec
0.0
05-26
Time Duration Step 10
0.0 to 65500 Sec
0.0
05-27
Time Duration Step 11
0.0 to 65500 Sec
0.0
05-28
Time Duration Step 12
0.0 to 65500 Sec
0.0
05-29
Time Duration Step 13
0.0 to 65500 Sec
0.0
05-30
Time Duration Step 14
0.0 to 65500 Sec
0.0
05-31
Time Duration Step 15
0.0 to 65500 Sec
0.0
05-32 Time
Unit
Settings
00: 1 Sec
01: 0.1 Sec
00
Group 6 Protection Function Parameters (Twice the value for 460V class)
Parameter
Functions
Settings
Factory
Setting
Customer
06-00 Over-voltage
Stall
Prevention
230V: 330.0~410.0VDC
460V: 660.0~820.0VDC
00: Disable
390.0
780.0
06-01 Over-current
Stall
Prevention during
Acceleration
20~150%
00: Disable
120
06-02 Over-current
Stall
Prevention during
operation
20~150%
00: Disable
120