English-14

Parameter

Functions

Settings

Factory

Setting

Customer

Bit 9: Master frequency source via analog
Bit10: Running command via communication

interface

Bit11: Parameter locked
Bit12~15: Reserved

00-03

Frequency Setting

Read only

Read

00-04

Output Frequency

Read only

Read

00-05

Output Current

Read only

Read

00-06

DC-BUS Voltage

Read only

Read

00-07 Output

Voltage

Read

only

Read

00-08

Output Power Factor Read only

Read

00-09

Output Power (kW)

Read only

Read

00-10 Feedback

Signal

Actual Value

Read only

Read

00-11

Feedback Signal (%) Read only

Read

00-12

User Target Value
(Low bit) uL 0-99.99

Read only

Read

00-13

User Target Value
(High bit) uH 0-9999

Read only

Read

00-14

PLC time

Read only

Read

Group 1 Basic Parameter (Twice the value for 460V class)

Parameter

Functions

Settings

Factory

Setting

Customer

01-00 Maximum

Output

Frequency

50.00~120.00Hz 60.00

01-01 Maximum

Voltage

Frequency (Base
Frequency)

0.10~120.00 Hz

60.00

01-02 Maximum

Output

Voltage

230V series: 0.1~255.0V
460V series: 0.2~510.0V

220.0
440.0

01-03

Mid-point Frequency

0.10~120 Hz

1.50

01-04

Mid-point Voltage

230V series: 0.1~255.0V
460V series: 0.2~510.0V

5.5

11.0

01-05 Minimum

Output

Frequency

0.10~20.00 Hz

1.50

01-06

Minimum Output Voltage 230V series: 0.1~50.0V

460V series: 0.2V~100.0V

5.5

11.0

01-07

Upper Bound Frequency 0.00~120.00 Hz

60.00

01-08

Lower Bound Frequency 0.00~120.00 Hz

0.00

a01-09 Acceleration Time 1

0.1~3600.0 Sec

10.0/

60.0

a01-10 Deceleration Time 1

0.1~3600.0 Sec

10.0/

60.0

a01-11 Acceleration Time 2

0.1~3600.0 Sec

10.0/

60.0

a01-12 Deceleration Time 2

0.1~3600.0 Sec

10.0/

60.0

a01-13 Acceleration Time 3

0.1~3600.0 Sec

10.0/

60.0