Delta Electronics AC Drive VFD-F Series User Manual
Page 13
English-13
SUMMARY OF PARAMETER SETTINGS
a: The parameter can be set during operation
Group 0 AC Drive Status Parameter
Parameter
Functions
Settings
Factory
Setting
Customer
00-00
Software Version
Read only
00-01
AC Drive Status
Indication 1
00: No Fault occurred
01: oc (over current)
02: ov (over voltage)
03: oH (over temperature)
04: oL (overload)
05: oL1 (electronic thermal relay)
06: EF (external Fault)
07: occ (AC drive IGBT fault)
08: cF3 (CPU failure)
09: HPF (Hardware Protection Failure)
10: ocA (current exceed during Acceleration)
11: ocd (current exceed during Deceleration)
12: ocn (current exceed during Steady State)
13: GFF (Ground Fault)
14: Lv (Low voltage)
15: cF1 (input data abnormal)
16: cF2 (output data abnormal)
17: bb (Base Block)
18: oL2 (over load2)
19: Reserved
20: codE (software or password protection)
21: EF1 (external Emergency Stop)
22: PHL (phase loss)
23: Lc (Low Current)
24: Fbl (Feedback Loss)
25: Reserved
26: FAnP (Fan Power Fault)
27: FF1 (Fan 1 fault)
28: FF2 (Fan 2 fault)
29: FF3 (Fan 3 fault)
30: FF123 (Fan 1, 2, 3 fault)
31: FF12 (Fan 1, 2 fault)
32: FF13 (Fan 1, 3 fault)
33: FF23 (Fan 2, 3 fault)
34: Fv (Gate Drive Low Voltage Protect)
Read
00-02
AC Drive Status
Indication 2
Bit 0~1: 00: Run led is off and stop led is on.
01: Run led is blink and stop led is on.
10: Run led is on and stop led is blink.
11: Run led is on and stop led is off.
Bit 2: 1: Jog on.
Bit 3~4: 00: Rev led is off and FWD led is on.
01: Rev led is blink and FWD led is on.
10: Rev led is on and FWD led is blink.
11: Rev led is on and FWD led is off.
Bit 5-7: Reserved
Bit 8: Master frequency source via
communication interface
Read