Delta Electronics AC Drive VFD-F Series User Manual
Page 12
English-12
Control Terminals Explanations
Terminal
Symbols
Terminal Functions
Factory Settings
FWD Forward-Stop
command
REV Reverse-Stop
command
EF External
fault
MI1 Multi-function
Input
1
Factory default: Multi-step speed command 1
MI2 Multi-function
Input
2
Factory default: Multi-step speed command 2
MI3 Multi-function
Input
3
Factory default: Multi-step speed command 3
MI4 Multi-function
Input
4
Factory default: Multi-step speed command 4
MI5 Multi-function
Input 5
Factory default: RESET
MI6
Multi-function Input 6
Factory default: JOG
MI7 Multi-function
Input
7
Factory default: Accel/Decel prohibit
MI8 Multi-function
Input
8
Factory
default: Accel/Decel time switch 1
+24V
DC Voltage Source
(+24V, 20mA), used for source mode.
DCM Digital
Signal
Common
Used as common for digital inputs and used for
sink mode.
RA 1
Multi-function Relay1 output (N.O.) a
RB 1
Multi-function Relay1 output (N.C.) b
RC 1
Multi-function Relay1 common
RA 2
Multi-function Relay2 output (N.O.) a
RB 2
Multi-function Relay2 output (N.C.) b
RC 2
Multi-function Relay2 common
1.5A(N.O.)/1A(N.C.) 240VAC
1.5A(N.O.)/1A(N.C.) 24VDC
Refer to Pr.03-00 to Pr.03-01
+10V
Potentiometer power source
+10V 20mA
AVI
Analog voltage Input
0 to +10V correspond to Max. operation
frequency
ACI 1/2 Analog current Input
4 to 20mA correspond to Max. operation
frequency
AFM 1
Analog frequency /current meter 1
0 to 10V correspond to Max. operation frequency
AFM 2
Analog frequency /current meter 2
4 to 20mA correspond to 2 times of output
current
ACM
Analog control signal (common)
* Control signal wiring size: 18 AWG (0.75 mm
2
).