beautypg.com

Delta Electronics AC Drive VFD-F Series User Manual

Page 12

background image

English-12

Control Terminals Explanations

Terminal

Symbols

Terminal Functions

Factory Settings

FWD Forward-Stop

command

REV Reverse-Stop

command

EF External

fault

MI1 Multi-function

Input

1

Factory default: Multi-step speed command 1

MI2 Multi-function

Input

2

Factory default: Multi-step speed command 2

MI3 Multi-function

Input

3

Factory default: Multi-step speed command 3

MI4 Multi-function

Input

4

Factory default: Multi-step speed command 4

MI5 Multi-function

Input 5

Factory default: RESET

MI6

Multi-function Input 6

Factory default: JOG

MI7 Multi-function

Input

7

Factory default: Accel/Decel prohibit

MI8 Multi-function

Input

8

Factory

default: Accel/Decel time switch 1

+24V

DC Voltage Source

(+24V, 20mA), used for source mode.

DCM Digital

Signal

Common

Used as common for digital inputs and used for
sink mode.

RA 1

Multi-function Relay1 output (N.O.) a

RB 1

Multi-function Relay1 output (N.C.) b

RC 1

Multi-function Relay1 common

RA 2

Multi-function Relay2 output (N.O.) a

RB 2

Multi-function Relay2 output (N.C.) b

RC 2

Multi-function Relay2 common

1.5A(N.O.)/1A(N.C.) 240VAC
1.5A(N.O.)/1A(N.C.) 24VDC
Refer to Pr.03-00 to Pr.03-01

+10V

Potentiometer power source

+10V 20mA

AVI

Analog voltage Input

0 to +10V correspond to Max. operation
frequency

ACI 1/2 Analog current Input

4 to 20mA correspond to Max. operation
frequency

AFM 1

Analog frequency /current meter 1

0 to 10V correspond to Max. operation frequency

AFM 2

Analog frequency /current meter 2

4 to 20mA correspond to 2 times of output
current

ACM

Analog control signal (common)

* Control signal wiring size: 18 AWG (0.75 mm

2

).