Specifications – Delta Electronics AC Drive VFD-F Series User Manual
Page 2
English-2
Specifications
Voltage Class
230V Class
Model Number VFD-XXXF23X
007
015
022
037
055
075
110
150
185
220
300
370
Max. Applicable Motor Output (kW)
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
Max. Applicable Motor Output (HP)
1.0
2.0
3.0
5.0
7.5
10
15
20
25
30
40
50
Rated Output Capacity (kVA)
1.9
2.5
4.2
6.5
9.5
12.5
18.3
24.7
28.6
34.3
45.7
55
Rated Output Current (A)
5.0
7.0
11
17
25
33
49
65
75
90
120
145
Maximum Output Voltage (V)
Proportional to Input Voltage
Rated Frequency (Hz)
0.10-120.00Hz
Ou
tp
u
t R
a
ti
n
g
Carrier Frequency (kHz)
4-10
3-9
2-6
Rated Input Current (A)
5.7
7.6
15.5
20.6
26
34
50
60
75
90
110
142
Rated Voltage
3-phase 180-264 V
Input
Rat
ing
Frequency Tolerance
47 – 63 Hz
Voltage Class
460V Class
Model Number
VFD-XXXF43X
007 015 022 037
055
075 110 150 185 220 300 370 450 550
750
900 1100 1320 1600 1850 2200
Max. Applicable Motor
Output (kW)
0.75 1.5 2.2 3.7
5.5
7.5
11
15
18.5
22
30
37 45 55
75
90
110
132
160
185
220
Max. Applicable Motor
Output (hp)
1.0 2.0 3.0 5.0
7.5
10
15
20
25
30
40
50 60 75
100
125
150
175
215
250
300
Rated Output
Capacity (kVA)
2.3 3.2 4.2 6.5
10
14
18
25
29
34
46
56 69 84
114
137
168
198
236
281
350
Rated Output
Current (A)
2.7 4.2 5.5 8.5
13
18
24
32
38
45
60
73 91 110
150
180
220
260
310
370
460
Maximum Output
Voltage (V)
3-phase Proportional to Input Voltage
Output Frequency
(Hz)
0.10-120.00Hz
Ou
tp
u
t R
a
ti
n
g
Carrier Frequency
(kHz)
4-10 3-9
2-6
3-phase
Rated Input
Current (A)
3.2 4.3 5.9 11.2
14
19
25
32
39
49
60
73 91 120 160 160
200
240
300
380
400
Rated Voltage
3-phase 342-528 V
Voltage Tolerance
-15~+10% (342-528 V)
Input Rat
ing
Frequency
Tolerance
± 5% (47~63Hz)
General Specification
Control System
SPWM (Sinusoidal Pulse Width Modulation, carrier frequency 2-10kHz)
Output Frequency Resolution
0.01Hz
Torque Characteristics
Including the auto-torque, auto-slip compensation; starting torque can be 150% at 1.0Hz
Overload Endurance
120% of rated current for 1 minute
Accel/Decel Time
1-36000/0.1-3600.0/0.01-360.00 seconds (3 Independent settings for Accel/Decel Time)
V/f Pattern
Adjustable V/f pattern
Cont
ro
l
Char
act
e
ri
st
ics
Stall Prevention Level
20 to 150%, Setting of Rated Current
Keypad
Setting by
Frequency
Setting
External Signal
1 set of AVI analog voltage DC0-+10V/0-+5V, 2 sets of ACI analog current 0/4-20mA,
15 Multi-Function Inputs, RS-485 interface (MODBUS), External terminals UP/DOWN
Key
Keypad
Set by RUN, STOP and JOG
Operation
Setting
Signal
External Signal
Operation by FWD, REV, JOG and communication operation
Multi-Function Input Signal
Multi-step selection 0 to 15, Jog, accel/decel inhibit, first to forth accel/decel switches,
counter, external Base Block (NC, NO), JOG, auxiliary motor start/maintenance
Multi-Function Output
Indication
AC Drive Operating, Frequency Attained, Desired Frequency Attained, Zero speed, Base
Block, Fault Indication, Local/Remote indication, and Auxiliary Motor Output
O
per
a
ting Char
ac
te
ri
st
ic
s
Analog Output Signal
2 sets of Analog frequency/current signal output