5-3-3 Example for a FAIL measurement:

Φ Trigger a new measurement.

Φ If the value is higher than the limit, an audible signal (2 beeps) sounds, the red

LED lights, and the DO7010 unit stays on the same test step.

Φ To re-test, trigger a new measurement either with the probe contact or the

green front panel push button.

Φ To store a FAIL measurement, press on the VALID function key.

Φ Confirm the validation by pressing on the YES function key.

Φ Then the DO7010 unit jumps to the next test step.

Φ To cancel the FAIL confirmation, press on the NO function key and trigger a

new measurement.

5-3-4 Example for an ABSENT point:

Φ If a point to be measured is absent or non available for the measurement, then

press on the ABSENT function key.

Φ Confirm the ABSENT status by pressing on the YES function key.

Φ Then the unit jumps to the next test step.

Φ To cancel the ABSENT confirmation, press on the NO function key and

trigger a new measurement.

ABCDE123456789

S:500.0mΩ

Ι:10Α

BAT:80%

154: ABS

POINT ABSENT

VALID

SET UP

ESC

ABCDE123456789

S:10.00mΩ

Ι:10Α

BAT:80%

153: 14.25

POINT ABSENT

VALID

SET UP

ESC

Operating Instructions

Digital Microhmmeter Type DO7010

27