Remote Condenser Location

Use the following for planning the placement of the

condenser relative to the ice machine
Location Limits - condenser location must not

exceed ANY of the following limits:

Maximum rise from the ice machine to the

condenser is 35 physical feet

Maximum drop from the ice machine to the

condenser is 15 physical feet

Physical line set maximum length is 100

feet.

Calculated line set length maximum is 150.

Calculation Formula:

Drop = dd x 6.6 (dd = distance in feet)

Rise = rd x 1.7 (rd = distance in feet)

Horizontal Run = hd x 1 (hd = distance in

feet)

Calculation: Drop(s) + Rise(s) + Horizontal

Run = dd+rd+hd = Calculated Line Length

Configurations that do NOT meet these

requirements must receive prior written

authorization from Scotsman.
Do NOT:

Route a line set that rises, then falls, then

rises.

Route a line set that falls, then rises, then

falls.

Calculation Example 1:
The condenser is to be located 5 feet below the ice

machine and then 20 feet away horizontally.
5 feet x 6.6 = 33. 33 + 20 = 53. This location would

be acceptable
Calculation Example 2:
The condenser is to be located 35 feet above and

then 100 feet away horizontally.
35 x 1.7 = 59.5. 59.5 +100 = 159.5. 159.5 is

greater than the 150 maximum and is NOT

acceptable.

22.87"

17.15"

40.35"

hd

rd

dd

Remote

Condenser

Located ABOVE

Ice Machine

Remote

Condenser

Located BELOW

Ice Machine

Condenser Distance &

Location Schematic

Max 35’

Max 15’