CME506R, 656R, 806R: AutoIQ Cubers

January 2000

Page 30

Problem or Symptom

Possible Cause

Probable Correction

Poor harvest

Hot gas valve does not open

Check for power to the coil, if

there is power, replace the hot

gas valve

Head pressure control valve

does not maintain enough

pressure (in freeze)

Replace the head pressure

control valve

Low capacity

High discharge pressure, from a

dirty condenser or faulty fan

motor

Clean the condenser, repair the

fan motor

Extreme hot location

Relocate the cabinet

Extremely hot condenser

location

Move condenser or provide

shade

Overcharge of refrigerant

Recover, evacuate and weigh in

the nameplate charge

Hot gas valve leaks thru, unit off

on refrigeration error

At the end of the freeze cycle,

there should be frost on the

evaporator end of the hot gas

inlet tube. If not, replace the hot

gas valve

Liquid and discharge lines are

in contact with each other

Separate and insulate them

Compressor cycles on and off

Low pressure (pump down)

control opening and closing

Check the low side pressure,

the liquid line valve must open

and the low side pressure must

rise over 35 PSIG before the

pump down control will close to

run the compressor.
Low on refrigerant, locate leak,

recover refrigerant, repair leak,

replace drier, evacuate and

weigh in the nameplate charge.

Compressor overheats

TXV superheat too high, check

charge, if charge is OK, replace

TXV
Mechanical fault with

compressor, replace

compressor
Internal relief valve opened,

check for cause of high

discharge pressure

Service Diagnosis