Service Diagnosis: Components

CME506R, 656R, 806R: AutoIQ Cubers

January 2000

Page 29

Problem or Symptom Possible Cause

Probable Correction

Fan motor does not

turn.

Open motor windings, or

seized bearings

Replace fan motor

No power to fan motor

KCMR230 relay points may be open. Wires

may be disconnected, contactor may not

close.

Pump motor does not

turn

Open motor windings, or

seized bearings

Replace pump

No power to pump

Check electrical connections. In Freeze,

Clean or Harvest the pump should have

power to it. If not, replace the AutoIQ

Controller.

Hot Gas Valve does

not open.

Open solenoid coil.

Replace hot gas valve

Stuck valve

Replace hot gas valve

No power to coil in Harvest Check wire connections, if ok, replace AutoIQ

Controller

Hot Gas Valve leaks

thru (warm tube

temperatures on both

sides of valve during

freeze)

Mechanical problem in

valve

Replace valve

Water Inlet Valve does

not open

Open solenoid coil

Replace valve

Stuck valve

Replace valve

No power to valve (early

part of harvest)

Check wire connections, if ok, replace AutoIQ

Controller

Water Inlet Valve does

not flow enough water

Restriction in water supply

Check water filters and/or inlet screen.

Water Inlet Valve

leaks thru

Mechanical problem in

valve

Replace valve

Compressor does not

work

Unit in Clean cycle

Push and release Freeze button.

Contactor coil open

Replace contactor

Liquid line valve coil open

Check and replace

No power to liquid line

valve coil

Check wiring and controller

Pump down control open

Check and replace

Open starting components Check and replace
Open windings

Check and replace compressor

Internal valve failure

Replace compressor