Ptcr diagnosis – Scotsman CME506R AutoIQ User Manual

Page 31

background image

PTCR Diagnosis

The CME506R, CME656R and CME806R D

Series all use a PTCR (Positive Temperature

Coefficient Resistor) in place of a conventional

start relay and start capacitor.

Power from the contactor connects to the

PTCR and to the Run Capacitor.

A wire connects the other terminal of the

PTCR to the compressor’s Start winding.

Another wire connects the run capacitor to

the start winding.

A parallel circuit connects power from the

contactor to the Run winding of the

compressor.

A PTCR changes resistance sharply when its

temperature changes. When the PTCR is cold, it

connects full current to the compressor’s start

winding. After a very short time the PTCR heats up

and shuts off the current flow. Under normal

operation, the PTCR’s case is at about 180

o

F.

At that temperature the PTCR has very high

resistance and will not allow current flow. It must

cool down to 120

o

F. before current will pass

through it again.

Diagnosis:
1. Disconnect electrical power.
2. Check if the PTCR is cool enough to handle

safely. If not, wait 5 minutes for it to cool off.
3. Disconnect both leads to the PTCR and

measure its resistance with an ohmmeter. If the

PTCR reads less than 22 ohms or more than 40

ohms, replace it.

CME506R, 656R, 806R: AutoIQ Cubers

January 2000

Page 31