Access Valves:

To use the access valves:
1. Be sure that the valve is closed. Remove the

stem cap and insert a 3/16" allen wrench. Check

that the valve is closed.
2. Remove the port cap and attach refrigerant

manifold hoses.
3. Open the valve and purge the hoses.

4. When service is complete, shut the discharge

access valve first. Then, with the machine running

and the middle hose outlet securely fastened to

the manifold or refrigerant tank (closed) open both

manifold valves. This allows any liquid refrigerant

in the discharge hose to flow thru the manifold and

into the suction side.
5. After the gages have equaled, shut the manifold

valves and the suction access valve.
6. Remove the gages and replace the stem and

port caps. Make certain that they are tightly closed.

Liquid Charging
Because R-404A is a near-azeotrope, only liquid

refrigerant can be used to recharge the

refrigeration system. To do that may take some

special techniques:
1. Use an electronic scale to measure the charge.
2. Place a drum or cylinder of R-404A on the

scale, valve side up (R-404A disposable cylinders

have an internal dip tube and dispense liquid

refrigerant from the valve when it is upright).
3. A refrigeration manifold should be attached to

the service access valves. Attach the charging

hose to the cylinder of R-404A. Open the cylinder’s

valve and purge the hose to the manifold.
4. Close the low side service access valve.
5. Open the discharge side manifold valve and

weigh in the name plate charge. After the charge is

weighed in, wait a few minutes and re-check the

scale.
6. If all of the refrigerant charge has not been

weighed into the discharge side, it must be

carefully added thru the low side. Close the

discharge service access valve.
7. With a sight glass or charge faster in the hose to

the low side port, start the ice machine.
8. Open the low side service access valve.
9. Crack open the low side manifold valve and

watch the scale and sight glass. Open and close

the low side manifold valve to flow liquid into the

manifold but flash off to vapor before it enters the

suction side of the refrigeration system. This

should only be a few ounces at most.
10. After the scale = the correct charge, shut off

the valve on the refrigerant cylinder.
11. With the ice machine running and the

discharge access valve closed, open both manifold

valves to allow the refrigerant in the hoses to enter

the system.
12. Shut the suction service access valve.
13. Remove the refrigeration manifold gages.
14. Replace and tighten all caps.

CME506R, 656R, 806R: AutoIQ Cubers

January 2000

Page 40

Allen

Wrench

Torque Stem

to 6-8 ft. lb.

Torque Stem Cap to

8-12 ft. lb.

Torque Core Cap

to 7-12 ft. lb.