beautypg.com

Bacnet pics statement – Orion System PT-Link II BACnet3 User Manual

Page 71

background image

PT-Link II BACnet3 Interface

10. BACNET PICS STATEMENT

71

10. BACnet PICS Statement

Segmentation Capability:

None

Object Types and Optional Properties Supported

Object Type

Optional Properties

Supported

Device Object

Location
Description
UTC Offset
Active COV Subscriptions

Analog Input

Reliability
Description

Analog Output

Reliability
Description
Max_Pres_Value
Min_Press_Value

Analog Output

Binary Input

Reliability
Description
Active_Test
Inactive_Test

Binary Output

Reliability
Description
Active_Test
Inactive_Test

Binary Value

Reliability
Description
Active_Test
Inactive_Test

Multi State Input

Reliability
Description
State_Test

Multi State Output

Reliability
Description
State_Test

Multi State Value

Reliability
Description
State_Test

Notifi cation Class Object

For all of these properties, the following applies:

1.) Does not support BACnet CreateObject

2.) Does not support BACnet DeleteObject

3.) No proprietary properties exist

Data Link Layer Options:

MS/TP master (Clause 9), baud rate up to 76.8 Kbps

MS/TP slave (Clause 9), baud rate up to 76.8 Kbps

Device Address Binding:

Not supported

Character Sets Supported:

Where support for multiple character sets is indicated, this does not
imply that they can all be supported simultaneously.

ISO 10646 (UTF-8) / ANSI X3.4