Parameter tables, 3 vcm-x wshp (tulsa) & rne bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual
Page 45
PT-Link II BACnet3 Interface
7. PARAMETER TABLES
45
7.3 VCM-X WSHP (Tulsa) & RNE BACnet Parameters
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
Parameter
Name
Object
Description
Limits
Remote VFD
Reset
RmVFDPos
AV:
258
Remote VFD
Position Reset
-1
100
Title 24 Econo-
mizer Alarms
AlmGrp5
AI: 391
Alarms for the 24
Title Economizer
Compressor A1
Low Suction
Pressure Alarm
A1LSPAlm
BI: 222
Alarm that
indicates
Suction Pressure
for Compressor
A1 is below the
Low Suction
Pressure
Cooling (Heat-
ing) Setpoint.
Compressor A1
Lockout Alarm
A1LktAlm
BI: 223
Alarm that
indicates
Compressor A1
is locked out.
Compressor A2
Low Suction
Pressure Alarm
A2LSPAlm
BI: 224
Alarm that
indicates
Suction Pressure
for Compressor
A2 is below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
Compressor A2
Lockout Alarm
A2LktAlm
BI: 225
Alarm that
indicates
Compressor A2
is locked out.
Compressor B1
Low Suction
Pressure Alarm
B1LSPAlm
BI: 226
Alarm that
indicates
Suction Pressure
for Compressor
B1 is below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
Compressor B1
Lockout Alarm
B1LktAlm
BI: 227
Alarm that
indicates
Compressor B1
is locked out.
Compressor B2
Low Suction
Pressure Alarm
B2LSPAlm
BI: 228
Alarm that
indicates
Suction Pressure
for Compressor
B2 is below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
Parameter
Name
Object
Description
Limits
Modulating
Compressor 2
MdCmp2
AI: 206
Current position
of the
2nd Stage of
Compressor
Modulation.
Head Pressure
Signal 1 on
Head Pressure
Module 1
HdPr1
AI: 207
Head Pressure
Signal 1 on
Head Pressure
Module 1
Head Pressure
Signal 2 on
Head Pressure
Module 1
HdPr2
AI: 208
Head Pressure
Signal 2 on
Head Pressure
Module 1
Condenser Fan
Signal 1 On
Head Pressure
Module 1
CdFan1
AI: 209
Condenser Fan
Signal 1 On
Head Pressure
Module 1
Condenser Fan
Signal 2 On
Head Pressure
Module 1
CdFan2
AI: 210
Condenser Fan
Signal 2 On
Head Pressure
Module 1
Water Temp. A
WaterTpA
AI: 220
Current water
temperature of
refrigerant for
System A.
Water Temp. B
WaterTpB
AI: 221
Current water
temperature of
refrigerant for
System B.
Condenser Fan
Signal 1 On
Head Pressure
Module 2
CdFan21
AI: 392
Condenser Fan
Signal 1 On
Head Pressure
Module 2
Condenser Fan
Signal 2 On
Head Pressure
Module 2
CdFan22
AI: 393
Condenser Fan
Signal 2 On
Head Pressure
Module 2
Head Pressure
Signal 1 on
Head Pressure
Module 2
HdPr21
AI: 394
Head Pressure
Signal 1 on
Head Pressure
Module 2
Head Pressure
Signal 2 on
Head Pressure
Module 2
HdPr22
AI: 395
Head Pressure
Signal 2 on
Head Pressure
Module 2