4. UPDATING THE SOFTWARE

PT-Link II BACnet3 Interface

20

4.2 Updating the Field Server Software

Figure 22: The FS-GUI Main Screen

1.) Extract and save the update fi le you receive from Field Server onto
your PC.

2.) Open your web browser, and type the IP Address of the PT-Link,
which defaults to

<192.168.1.24>

, and press

.

The GUI

will launch. Click

. The Main Screen

will appear. See Figure 22.

3.) In the Navigation Window on the left of the FS-GUI Screen, click

and then click

. See Figure 23.

Figure 23: Navigation Window - File Transfer

4.) Refer to the File Transfer Window below (Figure 24). In the General
Tab
, click

and locate the fi le you saved in Step 1. Then click

on

. When the download is complete, click on the

Restart>

button.

Figure 24: File Transfer - General Tab