Parameter tables, 6 sa controller bacnet parameters, Pt-link ii bacnet3 interface 54 – Orion System PT-Link II BACnet3 User Manual
Page 54: Zone
Zone
Zone
7. PARAMETER TABLES
PT-Link II BACnet3 Interface
54
7.6 SA Controller BACnet Parameters
BACnet Properties for SA Controller
Parameter
Name
Object
Description
Limits
Control
Status
CtrlSts
AI: 4
Current operational
status.
Occupied/
Mode
Enable
Cooling
Setpoint
Mirror
ClSt
AI: 7
Occupied/ Mode
Enable Cooling
Setpoint Mirror.
Control
Temperature
CtrlTp
AI: 9
Current value of the
control temperature
sensor.
Duct Static
Pressure
DuctPr
AI: 14
Current value of the
duct static pressure
sensor.
Economizer
Position
EcoPos
AI: 16
Current position
of the economizer
damper.
Occupied/
Mode
Enable
Heating
Setpoint
Mirror
HtSt
AI: 31
Occupied/ Mode
Enable Heating
Setpoint
Mirror.
Modulating
Gas Valve
Position
MdHt-
2Pos
AI: 38
Current position
of MODGAS II
modulating gas valve
control.
Reheat
Value
Position
Rt2Pos
AI: 60
Current position of
MHGRV modulating
hot gas reheat valve
control.
Indoor
Humidity
InRh
AI: 67
Current value of
the indoor humidity
sensor.
Space
Temperature
SpcTp
AI: 72
Current value of the
space temperature
sensor.
Current
Supply Air
Setpoint
SaTpStM
AI: 82
Current SAT
Cooling or Heating
setpoint if there is no
reset source;
Current calculated
SAT setpoint with
Reset Source.
Supply Air
Temperature
SaTp
AI: 83
Current value of the
supply air
temperature sensor.
Temperature
Demand
TpDmnd
AI: 84
Based on the
comparison between
the current Control
Temperature and the
Heating or Cooling
Setpoint Tempera-
tures. Does not work
for supply air control
VFD
Blower Fan
VfdBw-
Pos
AI: 88
Current position of
the VFD blower fan
signal.
BACnet Properties for SA Controller
Parameter
Name
Object
Description
Limits
Application
Software
Version
AppVer
AI: 99
Current version of the
software in the unit.
Coil
Temperature
Setpoint
CoilTpSt
AI: 107
Current Coil
Temperature
Setpoint.
Dewpoint
Setpoint
Mirror
DptStM
AI: 110
Mirror of the DPtSt
“read only.”
Indoor RH
Setpoint
Mirror
InRhStM
AI: 114
Mirror of the InRhSt
“read only.”
Modulating
Cool
Position
MdClPos
AI: 115
Current position of
the modulating
cooling signal
(Chilled water or
digital compressor).
Modulating
Heat
Position
MdHtPos
AI: 116
Current position of
the modulating
heating signal (hot
water or SCR heat).
Unit Mode
UnitMode
AI: 123
See Unit
Mode Bits
on page 57.
Coil
Temperature
CoilTp
AI: 181
Current coil
temperature reading
added on version
1.09.
Modulating
Compressor
2 Position
MdCmp2
AI: 206
Current position
of the 2nd Stage of
Compressor
Modulation.
Head
Pressure 1
HdPr1
AI: 207
Head Pressure for
1st unit.
Head
Pressure 2
HdPr2
AI: 208
Head Pressure for
2nd unit.
Entering Air
Temperature
EaTp
AI: 235
Temperature of the
air that is
entering the unit.
Entering
Water
Temperature
EwTp
AI: 236
Temperature of the
water that is
entering the unit.
Entering Air
Humidity
EaRh
AI: 237
Relative Humidity of
the Entering Air.
Coil
Temperature
2
CoilTp2
AI: 240
Current Coil
Temperature for 2nd
unit.
Entering Air
Dewpoint
EaDpt
AI: 241
Current Entering Air
Dewpoint
Water Side
Economizer
Bypass
WSEByp
AI: 242
Current Water Side
Economizer Bypass
Position for 1st unit.
Water Side
Economizer
Bypass 2
WSEByp2
AI: 243
Current Water Side
Economizer Bypass
Position for 2nd unit.
Condenser
Position 1
CdPos1
AI: 246
Current Condenser
Position for 1st unit.