Parameter tables, 1 vcb-x bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual
Page 39
PT-Link II BACnet3 Interface
7. PARAMETER TABLES
39
BACnet Properties for the VCB-X Controller
Param-
eter
Name
Object
Description
Limits
Low Sup-
ply Air
Tempera-
ture Alarm
LoSaAlm
BI: 37
The Supply Air
has fallen below
the Low SAT
Cutoff Setpoint
and cooling
stages will begin
to deactivate.
If the unit is in
Economizer,
Vent, or Heating
Mode the Supply
Fan will shut off.
Supply Air
Cooling
Setpoint
SaClSt
AV:77
Supply Air Cool-
ing Setpoint. If
Supply Air Reset
is confi gured,
this is the Low
SAT Cooling
Reset Value.
30
80
Supply Air
Cool High
Reset
SaClRt
AV: 324
If Supply Air Re-
set is confi gured,
this is the High
SAT Cooling
Reset Value.
0
100
Supply Air
Heat High
Reset
SaHtRt
AV: 325
If Supply Air Re-
set is confi gured,
this is the High
SAT Heating
Reset Value.
0
250
Supply Air
Heating
Setpoint
SaHtSt
AV:78
Supply Air Heat-
ing Setpoint. If
Supply Air Reset
is confi gured,
this is the Low
SAT Heating
Reset Value.
40
240
Supply Air
Tempera-
ture
SaTp
AI:83
Current value of
the Supply Air
Temperature
Sensor.
Bad
Supply Air
Tempera-
ture Sensor
SaTpAlm
BI: 2
Indicates a fail-
ure of the Supply
Air Temperature
Sensor.
Low
Supply
Air Temp
Cutoff
LoSaCf
AV: 344
Cooling will be
disabled if the
Supply Air Tem-
perature falls
below this value.
See sequence for
more details.
0
100
High
Supply
Air Temp
Cutoff
HiSaCf
AV: 345
Heating will be
disabled if the
Supply Air Tem-
perature rises
above this value.
See sequence for
more details.
0
250
BACnet Properties for the VCB-X Controller
Param-
eter
Name
Object
Description
Limits
Smoke
Alarm /
Emergency
Shutdown
SmokeAlm
BI: 119
Indicates the
Smoke sensor
has been acti-
vated. This will
shut down the
unit.
Space
Tempera-
ture
SpcTp
AI:72
Current value of
the space tem-
perature sensor.
Space
Tempera-
ture Offset
SpcTpOst
AV:71
If the Space
Temperature
Sensor is reading
incorrectly, use
this option to
enter an offset
to adjust the
Sensor’s
Temperature.
-100
100
Space
Tempera-
ture Sensor
Lost
SpcTpAlm
BI: 101
Indicates
a failure of the
Space Tempera-
ture Sensor.
Static
Pressure
StaticPr
AI:270
Current Static
Pressure.
Static
Pressure
Setpoint
StatPrSt
AV:290
Current Static
Pressure
Setpoint.
.10
3.0
Static
Pressure
Setpoint
Deadband
DuctPrDb
AV:357
Value above and
below the Duct
Static Pressure
Setpoint where
no control
change occurs.
.01
0.5
Suction
Pressure
SucPr
AI: 333
Current Suction
Pressure value.
High
Suction
Pressure
Alarm
HiSucPr
BI: 352
Indicates
Suction Pressure
is above the
High Suction
Pressure Cool-
ing (Heating)
Setpoint.
Low
Suction
Pressure
Alarm
LoSucPr
BI: 383
Indicates
Suction Pressure
is below the Low
Suction Pressure
Cooling (Heat-
ing) Setpoint.
Supply Air
CFM
SaCFM
AI:195
Current Supply
Airfl ow
Measurement.
High
Supply Air
Tempera-
ture Alarm
HiSaAlm
BI: 33
The Supply Air
has risen above
the High SAT
Cutoff Setpoint.
Heating stages
begin to deacti-
vate and the fan
continues to run.
7.1 VCB-X BACnet Parameters