PT-Link II BACnet3 Interface

7. PARAMETER TABLES

39

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Low Sup-

ply Air

Tempera-

ture Alarm

LoSaAlm

BI: 37

The Supply Air

has fallen below

the Low SAT

Cutoff Setpoint

and cooling

stages will begin

to deactivate.

If the unit is in

Economizer,

Vent, or Heating

Mode the Supply

Fan will shut off.

Supply Air

Cooling

Setpoint

SaClSt

AV:77

Supply Air Cool-

ing Setpoint. If

Supply Air Reset

is confi gured,

this is the Low

SAT Cooling

Reset Value.

30

80

Supply Air

Cool High

Reset

SaClRt

AV: 324

If Supply Air Re-

set is confi gured,

this is the High

SAT Cooling

Reset Value.

0

100

Supply Air

Heat High

Reset

SaHtRt

AV: 325

If Supply Air Re-

set is confi gured,

this is the High

SAT Heating

Reset Value.

0

250

Supply Air

Heating

Setpoint

SaHtSt

AV:78

Supply Air Heat-

ing Setpoint. If

Supply Air Reset

is confi gured,

this is the Low

SAT Heating

Reset Value.

40

240

Supply Air

Tempera-

ture

SaTp

AI:83

Current value of

the Supply Air

Temperature

Sensor.

Bad

Supply Air

Tempera-

ture Sensor

SaTpAlm

BI: 2

Indicates a fail-

ure of the Supply

Air Temperature

Sensor.

Low

Supply

Air Temp

Cutoff

LoSaCf

AV: 344

Cooling will be

disabled if the

Supply Air Tem-

perature falls

below this value.
See sequence for

more details.

0

100

High

Supply

Air Temp

Cutoff

HiSaCf

AV: 345

Heating will be

disabled if the

Supply Air Tem-

perature rises

above this value.
See sequence for

more details.

0

250

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Smoke

Alarm /

Emergency

Shutdown

SmokeAlm

BI: 119

Indicates the

Smoke sensor

has been acti-

vated. This will

shut down the

unit.

Space

Tempera-

ture

SpcTp

AI:72

Current value of

the space tem-

perature sensor.

Space

Tempera-

ture Offset

SpcTpOst

AV:71

If the Space

Temperature

Sensor is reading

incorrectly, use

this option to

enter an offset

to adjust the

Sensor’s

Temperature.

-100

100

Space

Tempera-

ture Sensor

Lost

SpcTpAlm

BI: 101

Indicates

a failure of the

Space Tempera-

ture Sensor.

Static

Pressure

StaticPr

AI:270

Current Static

Pressure.

Static

Pressure
Setpoint

StatPrSt

AV:290

Current Static

Pressure

Setpoint.

.10

3.0

Static

Pressure
Setpoint

Deadband

DuctPrDb

AV:357

Value above and

below the Duct

Static Pressure

Setpoint where

no control

change occurs.

.01

0.5

Suction

Pressure

SucPr

AI: 333

Current Suction

Pressure value.

High

Suction

Pressure

Alarm

HiSucPr

BI: 352

Indicates

Suction Pressure

is above the

High Suction

Pressure Cool-

ing (Heating)

Setpoint.

Low

Suction

Pressure

Alarm

LoSucPr

BI: 383

Indicates

Suction Pressure

is below the Low

Suction Pressure

Cooling (Heat-

ing) Setpoint.

Supply Air

CFM

SaCFM

AI:195

Current Supply

Airfl ow

Measurement.

High

Supply Air

Tempera-

ture Alarm

HiSaAlm

BI: 33

The Supply Air
has risen above

the High SAT

Cutoff Setpoint.

Heating stages

begin to deacti-

vate and the fan

continues to run.

7.1 VCB-X BACnet Parameters

This manual is related to the following products: