Parameter tables, 6 sa controller bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual
Page 57: 1 sa controller pt-link-bacnet, Property identifi er

PT-Link II BACnet3 Interface
7. PARAMETER TABLES
57
7.6 SA Controller BACnet Parameters
BACnet Properties for SA Controller
Parameter
Name
Object
Description
Drain Pan
Overfl ow
DrnAlm
BI: 244
Alarm that indicates overfl ow of
the drain pan.
Proof of
Water Flow
Alarm
PoWFAlm
BI: 245
Alarm that indicates no
Proof of Water Flow.
Entering Air
Temperature
Alarm
EaTpAlm
BI: 248
Alarm that indicates
failure in the Entering Air
Temperature Sensor.
BACnet Properties for SA Controller
Parameter
Name
Object
Description
Control
Temperature
Heat Failure
CtrlTpHF
BI: 109
This alarm is activated if the
control temperature does not
get within 5°F to the occupied
heating setpoint in an hour in the
heating mode. This alarm is not
used in 100% outside air units or
supply air control.
Space
Temperature
Sensor Lost
SpcTpAlm
BI: 101
Alarm that indicates a failure in
the space temperature sensor.
On Board
Relay 1
OnRly1
BI: 127
Current status of relay 1.
On Board
Relay 2
OnRly2
BI: 128
Current status of relay 2.
On Board
Relay 3
OnRly3
BI: 129
Current status of relay 3.
On Board
Relay 4
OnRly4
BI: 130
Current status of relay 4.
On Board
Relay 5
OnRly5
BI: 131
Current status of relay 5.
Expansion
Relay 1
ExRly1
BI: 133
Current status of relay 6.
Expansion
Relay 2
ExRly2
BI: 134
Current status of relay 7.
Expansion
Relay 3
ExRly3
BI: 135
Current status of relay 8.
Expansion
Relay 4
ExRly4
BI: 136
Current status of relay 9.
Expansion
Relay 5
ExRly5
BI: 137
Current status of relay 10.
Expansion
Relay 6
ExRly6
BI: 138
Current status of relay 11.
Expansion
Relay 7
ExRly7
BI: 139
Current status of relay 12.
Expansion
Relay 8
ExRly8
BI: 140
Current status of relay 13.
Expansion
Relay 9
ExRly9
BI: 141
Current status of relay 14.
Expansion
Relay 10
ExRly10
BI: 142
Current status of relay 15.
Expansion
Relay 11
ExRly11
BI: 143
Current status of relay 16.
Expansion
Relay 12
ExRly12
BI: 144
Current status of relay 17.
Expansion
Relay 13
ExRly13
BI: 145
Current status of relay 18.
Expansion
Relay 14
ExRly14
BI: 146
Current status of relay 19.
Expansion
Relay 15
ExRly15
BI: 147
Current status of relay 20.
Expansion
Relay 16
ExRly16
BI: 148
Current status of relay 21.
Emergency
Shutdown
Alarm
EmerAlm
BI: 219
Alarm that indicates
Emergency Shutdown.
7.6.1 SA Controller PT-Link-BACnet
®
Property Identifi er:
The PT-Link-BACnet
®
Link amends the following property identity to
the BACnet
®
property identifi er.
BACNETPropertyIdentifi er :
SAUnitMode ::= ENUMERATED {
Unoccupied
(0),
RemoteContactOccupied (1),
NormalScheduleOccupied
(2),
PushButtonOrZoneOverride
(3),
HolidayModeActive
(4),
UnoccupiedZoneDemand
(5),
RemoteScheduleOverride (6),
CurrentOutputForceMode
(7),
SATHighOrLowCutOff
(8),
CO2OverrideInProgress
(9),
PurgeModeActive
(10)
}
SAControlStatusBits ::= ENUMERATED {
Off
(0),
Vent
(1),
Cool
(2),
Heat
(3),
Dehum
(4),
Dehum
Cool
(5),
Dehum
Heat
(6),
Warm
Up
Mode
(7)
}