7. PARAMETER TABLES
PT-Link II BACnet3 Interface
60
BACnet Properties for the VCM Controller
Parameter
Name
Object
Description
Limits
Schedule
Force
SchdFrc
AV: 66
0 = Auto/
Unoccupied Mode
1 = Forced On
2 = Forced Off
0
2
Space
Sensor
Offset
SpcTpOst
AV: 71
If the Space
Temperature
Sensor is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
-100
100
SAT/Reset
Source
Cooling
Setpoint
SaClSt
AV: 77
Supply Air setpoint
or Reset Source tar-
get temperature in
Cooling Mode.
40
80
SAT/Reset
Source
Heating
Setpoint
SaHtSt
AV: 78
Supply Air setpoint
or Reset Source tar-
get temperature in
Heating Mode.
40
200
Supply
Air Sensor
Offset
SaTpOst
AV: 80
If the Supply Air
Temperature
Sensor is reading
incorrectly, you can
use this option to
enter an offset
temperature to
adjust the Sensor’s
Temperature.
-100
100
Unoccupied
Cooling
Offset
UnClOst
AV: 124
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied
Cooling Setpoint
out by a user
adjustable amount.
If you do not want
Cooling to operate
during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
0
30
Unoccupied
Heating
Offset
UnHtOst
AV: 125
During the
Unoccupied Mode
of Operation, this
Setpoint spreads
the Occupied
Heating Setpoint
out by a user
adjustable amount.
If you do not want
Heating to operate
during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
0
30
BACnet Properties for the VCM Controller
Parameter
Name
Object
Description
Limits
Dewpoint
Setpoint
DptSt
AV: 13
If the outdoor
dewpoint rises
above this setpoint,
the unit will
activate the
Dehumidifi cation
Demand.
35
80
Coil
Temperature
Setpoint
CoilTpSt
AV: 107
This is the coil
suction temperature
target during
dehumidifi cation
mode. Produces
dewpoint in the
supply air
approximately
10°F above this
setpoint.
35
70
Indoor
Humidity
Setpoint
InRhSt
AV: 120
If the indoor
humidity rises
above this setpoint,
the unit will
activate the
Dehumidifi cation
Demand.
0
100
Warm Up
Setpoint
WmupSt
AV: 91
In a VAV
application, upon
entering the
occupied mode, the
Warm-up Demand
will be activated
if the return air
temperature falls
one degree below
this setpoint.
50
90
Wet Bulb
Setpoint
WtblSt
AV: 92
The economizer is
enabled if the out-
door temperature or
wetbulb falls below
this setpoint.
0
80
Bad Supply
Air Sensor
SaTpAlm
BI: 2
Alarm that
indicates a failure
in the
supply air sensor.
CO
2
Sensor
Installed
CO2Cfg
BI: 3
Status that
indicates the CO
2
function has been
confi gured.
Cooling
Demand
ClDmnd
BI: 5
Status that
indicates a demand
for cooling.
Cooling
Enabled
ClEnbl
BI: 6
Status that indicates
mechanical cooling
is enabled.
Economizer
Enabled
EcoEnbl
BI: 15
Status that indicates
the economizer is
enabled.
7.7 VCM BACnet Parameters