7. PARAMETER TABLES

PT-Link II BACnet3 Interface

60

BACnet Properties for the VCM Controller

Parameter

Name

Object

Description

Limits

Schedule

Force

SchdFrc

AV: 66

0 = Auto/

Unoccupied Mode

1 = Forced On

2 = Forced Off

0

2

Space

Sensor

Offset

SpcTpOst

AV: 71

If the Space

Temperature

Sensor is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

SAT/Reset

Source

Cooling

Setpoint

SaClSt

AV: 77

Supply Air setpoint

or Reset Source tar-

get temperature in

Cooling Mode.

40

80

SAT/Reset

Source

Heating

Setpoint

SaHtSt

AV: 78

Supply Air setpoint

or Reset Source tar-

get temperature in

Heating Mode.

40

200

Supply

Air Sensor

Offset

SaTpOst

AV: 80

If the Supply Air

Temperature

Sensor is reading

incorrectly, you can

use this option to

enter an offset

temperature to

adjust the Sensor’s

Temperature.

-100

100

Unoccupied

Cooling

Offset

UnClOst

AV: 124

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Cooling Setpoint

out by a user

adjustable amount.

If you do not want
Cooling to operate

during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30

Unoccupied

Heating

Offset

UnHtOst

AV: 125

During the

Unoccupied Mode

of Operation, this

Setpoint spreads

the Occupied

Heating Setpoint

out by a user

adjustable amount.

If you do not want
Heating to operate

during the

Unoccupied Mode,

use the default

setting of 30°F for

these setpoints.

0

30

BACnet Properties for the VCM Controller

Parameter

Name

Object

Description

Limits

Dewpoint

Setpoint

DptSt

AV: 13

If the outdoor

dewpoint rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

35

80

Coil

Temperature

Setpoint

CoilTpSt

AV: 107

This is the coil

suction temperature

target during

dehumidifi cation

mode. Produces

dewpoint in the

supply air

approximately

10°F above this

setpoint.

35

70

Indoor

Humidity

Setpoint

InRhSt

AV: 120

If the indoor

humidity rises

above this setpoint,

the unit will

activate the

Dehumidifi cation

Demand.

0

100

Warm Up

Setpoint

WmupSt

AV: 91

In a VAV

application, upon

entering the

occupied mode, the

Warm-up Demand

will be activated

if the return air

temperature falls

one degree below

this setpoint.

50

90

Wet Bulb

Setpoint

WtblSt

AV: 92

The economizer is

enabled if the out-

door temperature or
wetbulb falls below

this setpoint.

0

80

Bad Supply

Air Sensor

SaTpAlm

BI: 2

Alarm that

indicates a failure

in the

supply air sensor.

CO

2

Sensor

Installed

CO2Cfg

BI: 3

Status that

indicates the CO

2

function has been

confi gured.

Cooling

Demand

ClDmnd

BI: 5

Status that

indicates a demand

for cooling.

Cooling
Enabled

ClEnbl

BI: 6

Status that indicates
mechanical cooling

is enabled.

Economizer

Enabled

EcoEnbl

BI: 15

Status that indicates

the economizer is

enabled.

7.7 VCM BACnet Parameters