Parameter tables, 1 vcb-x bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual
Page 43: Property identifi er
![background image](https://www.manualsdir.com/files/800365/content/doc043.png)
PT-Link II BACnet3 Interface
7. PARAMETER TABLES
43
7.1.1 VCB-X PT-Link II BACnet
®
Property Identifi er:
The PT-Link II BACnet
®
Link amends the following property identity
to the BACnet
®
property identifi er.
BACNETPropertyIdentifi er :
VcbxUnitMode ::= ENUMERATED {
Unoccupied
(0)
Occupied
(1),
Override
Mode
(2),
Holiday
Unoccupied
(3),
Holiday
Occupied
(4),
Forced
Occupied
(5),
Forced
Unoccupied
(6),
}
VcbxControlStatusBits ::= ENUMERATED {
Off
(0),
Vent
Mode
(1),
Cooling
Mode
(2),
Heating
Mode
(3),
Vent
RH
Mode (4),
Cooling
RH
Mode
(5),
Heating
RH
Mode
(6),
Warm
Up
Mode
(7),
Defrost
Mode
(8),
Purge
Mode
(9),
Cool
Down
Mode
(10),
Remote
Cooling
Mode
(11),
Remote
Heating
Mode
(12),
Remote
Vent
Dehum
(13),
Remote
Cool
Dehum
(14),
Remote
Heat
Dehum
(15)
}
VcbxAlarmGroup1Bits ::= BIT STRING {
Bad
Supply
Air
Sensor
(0),
Bad
Return
Air
Sensor
(1),
Bad
Outside
Air
Sensor
(2),
Bad
Space
Sensor
(3),
Bad Main Expansion Board
(4),
Bad
Coil
Temp
Sensor
(5),
Bad
Co2
Sensor
(6),
Bad
Discharge
Sensor
(7),
Bad
OA
CFM
Sensor
(8),
Bad Exhaust CFM Sensor
(9),
Bad Supply CFM Sensor
(10),
Bad
Return
CFM
Sensor
(11),
Bad
Reheat
Module (12),
Bad
ModGas
Module
(13),
Bad Relay Expansion Module
(14),
Missing EM2 Expansion Board
(15)
}
VcbxAlarmGroup2Bits ::= BIT STRING {
Mechanical Cooling Failure
(0),
Mechanical
Heating
Failure
(1),
Fan
Proving
Alarm
(2),
Dirty
Filter
Alarm
(3),
Emergency
Shutdown
Alarm
(4),
Economizer Air Temperature Failure
(5),
Not Economizing When It Should
(6),
Economizing When It Should Not
(7),
Economizer Damper Failure
(8),
Economizer Excess Outdoor Air
(9)
}
VcbxAlarmGroup3Bits ::= BIT STRING {
High Supply Air Cutoff
(0),
Low
Supply
Air
Cutoff
(1),
High Control Mode Signal Alarm
(2),
Low Control Mode Signal Alarm
(3),
Digital Compressor Cutoff Alarm
(4),
Digital Compressor Lockout Alarm
(5),
High
Head
Pressure (6),
Loop Water Proof of Flow
(7),
Low
Suction
Pressure
(8),
Unsafe Suction Pressure
(9),
Low
Leaving
Water
Temp
(10)
}
VcbxOnBoardRelaysBits ::= BIT STRING {
On
Board
Relay
1
(0),
On
Board
Relay
2
(1),
On
Board
Relay
3
(2),
On
Board
Relay
4
(3),
On
Board
Relay
5
(4)
On
Board
Relay
6
(5)
}
7.1 VCB-X BACnet Parameters