Parameter tables, 4 vcm-x wshp (coil) bacnet parameters, Pt-link ii bacnet3 interface – Orion System PT-Link II BACnet3 User Manual
Page 47
![background image](https://www.manualsdir.com/files/800365/content/doc047.png)
PT-Link II BACnet3 Interface
7. PARAMETER TABLES
47
7.4 VCM-X WSHP (Coil) BACnet Parameters
BACnet Properties for VCM-X WSHP (Coil)
Parameter
Name
Object
Description
Limits
Proof of Water
Flow Alarm
POWF1Alm
BI: 232
Alarm that
indicates no
Proof of Water
Flow.
Module
Communica-
tions
Alarm
ComMAlm
BI: 234
Alarm that
indicates that
one or more
Modules are
not commu-
nicating with
the VCM-X
WSHP
Controller.
Bad Return Air
Sensor
RaTpAlm
BI: 365
Alarm that
indicates
a failure in
the Return Air
Sensor.
Title 24 Econo-
mizer Feedback
T24EcFb
AI: 384
Current
position of
feedback from
Economizer
actuator.
Title 24
Sensor Alarm
T24TpAlm
BI: 385
Outside Air
or Supply Air
Temperature
Sensor is
shorted or
missing.
Title 24 Not
Economizing
When It Should
T24NEWS
BI: 386
Economizer
is enabled but
not following
the desired
Economizer
position com-
manded.
Title 24 Econo-
mizing When It
Should Not
T24EWISN
BI: 387
Economizer
is not enabled
but the feed-
back signal
indicates a
position more
open than the
minimum.
Title 24 Damper
Failure
T24DpAlm
BI: 388
Economizer
is enabled but
not within
10% of de-
sired position
within 150
seconds.
Title 24 Excess
Outdoor Air
T24ExsOA
BI: 389
Economizer
feedback
is lost or
Economizer is
not following
commanded
position.
BACnet Properties for VCM-X WSHP (Coil)
Parameter
Name
Object
Description
Limits
Modulating
Compressor 2
MdCmp2
AI: 206
Current
position of the
2nd Stage of
Compressor
Modulation.
Head Pressure 1
HdPr1
AI: 207
Head Pressure
for
1st
Compressor
Head Pressure 2
HdPr2
AI: 208
Head Pressure
for
2nd
Compressor
Condenser
Fan 1
CdFan1
AI: 209
Condenser
Fan 1
Signal Status
Condenser
Fan 2
CdFan2
AI: 210
Condenser
Fan 2
Signal Status
Water Temp. A
WaterTpA
AI: 220
Current water
temperature.
Remote VFD
Reset
RmVFDPos
AV:
258
Remote VFD
Position Reset
-1
100
Compressor A
Low Suction
Pressure Alarm
A1LSPAlm
BI: 222
Alarm that
indicates
Suction
Pressure for
Circuit A is
below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
Compressor A
Lockout Alarm
A1LktAlm
BI: 223
Alarm that in-
dicates Circuit
A Compres-
sors are locked
out.
Compressor B
Low Suction
Pressure Alarm
B1LSPAlm
BI: 226
Alarm that
indicates
Suction
Pressure for
Circuit B is
below the
Low Suction
Pressure Cool-
ing (Heating)
Setpoint.
Compressor B
Lockout Alarm
B1LktAlm
BI: 227
Alarm that in-
dicates Circuit
B Compres-
sors are locked
out.
Low Water
Temperature
Alarm
LWT1Alm
BI: 230
Alarm that
indicates water
temperature
is below the
Leaving Water
Safety Set-
point (Heating
only).