7. PARAMETER TABLES

PT-Link II BACnet3 Interface

40

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Supply Air

Tempera-

ture Offset

SaTpOst

AV:80

If the Supply Air

Temperature

Sensor is reading

incorrectly, use

this offset to ad-

just the Sensor’s

Temperature.

-100

100

Current

Supply Air

Tem-

perature
Setpoint

SaTpStM

AI: 82

Current SAT

Cooling or

Heating

setpoint if there

is no reset

source;

Current cal-

culated SAT

setpoint with

Reset Source.

Cooldown

Mode

Supply Air

Setpoint

SaCldnSt

AV: 362

Cooling will be

controlled to

this Supply Air

Setpoint during

Cool-Down.

30

80

Missing

Supply

Air CFM

Sensor

SaCfmSr

BI: 372

Indicates the

Supply Air CFM

Sensor is not

detected.

Warmup

Mode

Supply Air

Setpoint

SaWmupSt

AV: 361

Heating will be

controlled to

this Supply Air

Setpoint during

Morning Warm-

Up.

40

240

SZ VAV

Integral

Constant

SZVAVFnl

AV: 360

This is the

Integral Constant

for controlling

the SZ VAV Fan

Speed.

0

10

Title 24

Econo-

mizer

Feedback

T24EcFb

AI: 384

Current position

of feedback from

Economizer

actuator.

Title 24

Sensor

Alarm

T24TpAlm

BI: 385

Outside Air

or Supply Air

Temperature

Sensor is shorted

or missing.

Title

24 Not

Economiz-

ing When

It Should

T24NEWS

BI: 386

Economizer is

enabled but not

following the

desired Econo-

mizer position

commanded.

Title 24

Economiz-

ing When

It Should

Not

T24EWISN

BI: 387

Economizer is

not enabled but

the feedback

signal indicates
a position more

open than the

minimum.

BACnet Properties for the VCB-X Controller

Param-

eter

Name

Object

Description

Limits

Title 24

Damper

Failure

T24DpAlm

BI: 388

Economizer is

enabled but not

within 10% of

desired position

within 150

seconds.

Title 24

Excess

Outdoor

Air

T24ExsOA

BI: 389

Economizer

feedback is lost

or Economizer

is not follow-

ing commanded

position.

Unoc-

cupied

Cooling

Offset

UnClOst

AV: 124

In Unoccupied

Mode, this

offsets the

Occupied Cool-

ing Setpoint by

this user adjust-

able amount. If
no Unoccupied

Cooling is

desired, use the

default setting

of 30°F for this

setpoint.

0

30

Unoc-

cupied

Heating

Offset

UnHtOst

AV:125

In Unoccupied

Mode, this

offsets the

Occupied Heat-

ing Setpoint by

this user adjust-

able amount. If
no Unoccupied

Heating is

desired, use the

default setting

of 30°F for this

setpoint.

0

30

VFD

Position

VfdBwPos

AI:88

Current

position of the

VFD blower fan

signal.

VFD Min

Position in

Cool Mode

VFDClMin

AV: 319

In Single Zone

VAV confi gura-

tion, this is the

fan speed at

which the VFD

will start when

Cooling is

initiated. In a

VAV confi gura-

tion this is the

lowest fan speed

allowed in the

Cooling Mode.

In CAV and

MUA confi gura-

tions this should

be set to 100%.

0%

100%

7.1 VCB-X BACnet Parameters