Parameter tables, 5 vcm-x bacnet parameters, Pt-link ii bacnet3 interface 50 – Orion System PT-Link II BACnet3 User Manual
Page 50: Zone
Zone
Zone
7. PARAMETER TABLES
PT-Link II BACnet3 Interface
50
7.5 VCM-X BACnet Parameters
BACnet Properties for the VCM-X Controller
Parameter
Name
Object
Description
Limits
Warm Up
Setpoint
WmupSt
AV: 91
In a VAV
application, upon
entering the oc-
cupied mode, the
Warm-up Demand
will be activated
if the return air
temperature falls
one degree below
this setpoint.
50
90
Wet Bulb
Setpoint
WtblSt
AV: 92
The economizer is
enabled if the
outdoor tempera-
ture or wetbulb falls
below this setpoint.
0
80
Coil
Temperature
Setpoint
CoilTpSt
AV: 107
This is the coil
suction temperature
target during
dehumidifi cation
mode. Produces
dewpoint in the
supply air
approximately 10°F
above this setpoint.
35
70
Relief
Pressure
Setpoint
RfPrSt
AV: 118
This is the target
building pressure
to be maintained
by the VFD Relief
signal.
-0.2
0.2
Indoor
Humidity
Setpoint
InRhSt
AV: 120
If the indoor
humidity rises
above this setpoint,
the unit will acti-
vate the Dehumidi-
fi cation Demand.
0
100
Unoccupied
Cooling
Offset
UnClOst
AV: 124
During the
Unoccupied Mode
of Operation, this
Setpoint spreads the
Occupied Cooling
Setpoint out by
a user adjustable
amount. If you do
not want Cooling to
operate during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
0
30
Unoccupied
Heating
Offset
UnHtOst
AV: 125
During the
Unoccupied Mode
of Operation, this
Setpoint spreads the
Occupied Heating
Setpoint out by
a user adjustable
amount. If you do
not want Heating to
operate during the
Unoccupied Mode,
use the default
setting of 30°F for
these setpoints.
0
30
BACnet Properties for the VCM-X Controller
Parameter
Name
Object
Description
Limits
CO
2
Setpoint
CO2St
AV: 149
When the CO
2
level rises above
the CO
2
Protection
Limit Max Level,
the Economizer’s
Minimum Position
will begin to reset
open proportionally
between the CO
2
Protection Limit
Max Level Setpoint
and the Reset
Range Setpoint.
0
3000
Minimum
Outside Air
Setpoint
MinEcoSt
AV: 151
This is the
minimum position
of the economizer
in the occupied
modes.
1
100
Static
Pressure
Setpoint
DuctPrSt
AV: 152
This is the target
duct pressure to be
maintained by the
VFD blower signal.
0.01
3
Preheater
Setpoint
PreHtSp
AV: 196
Low Outside Air
Ambient
Protection Setpoint
0
100
Outdoor
Air CFM
Setpoint
OACfmSt
AV: 203
Minimum desired
Outdoor Air CFM.
0.10
K
200 K
Outdoor Air
CFM Reset
Limit
OACfmRs
AV: 204
Maximum desired
Outdoor Air CFM
when CO
2
reaches
its reset limit.
0.10
K
200 K
Supply Air
Cool High
Reset
SaClRt
AV: 324
High Supply Air
Cooling Reset
Limit
40
150
Supply Air
Heat High
Reset
SaHtRt
AV: 325
High Supply Air
Heating Reset Limit
40
150
Cooling
Low Reset
Source
ClLoRt
AV: 326
Low Cool Reset
Source Setpoint
1
150
Cooling
High Reset
Source
ClHiRt
AV: 327
High Cool Reset
Source Setpoint
1
150
Heating
Low Reset
Source
HtLoRt
AV: 328
Low Heat Reset
Source Setpoint
1
150
Heating
High Reset
Source
HtHiRt
AV: 329
High Heat Reset
Source Setpoint
1
150