7. PARAMETER TABLES
PT-Link II BACnet3 Interface
34
7.1 VCB-X BACnet Parameters
BACnet Properties for the VCB-X Controller
Param-
eter
Name
Object
Description
Limits
Cooling
High Reset
Source
ClHiRt
AV: 327
If doing Supply
Air Setpoint
Reset, this is
the High Reset
Source value in
Cooling that will
correspond to
the Supply Air
Cooling Setpoint
(Low Reset).
1
150
Condenser
Control
Signal
CdCtrSg1
AI:280
Condenser Fan
Signal 1 Status.
Controlling
Sensor
High
Alarm
Offset
CTpHiAlm
AV: 349
If the tem-
perature of the
controlling sen-
sor rises above
the Occupied
Cooling Setpoint
by this value,
a High Control
Temp Alarm
will occur. Only
applies if confi g-
ured for Space
or Return Air
Temp Control, or
as Single Zone
VAV.
0
50
Controlling
Sensor
Low Alarm
Offset
CTpLoAlm
AV: 350
If the tempera-
ture of the con-
trolling sensor
falls below the
Occupied Heat-
ing Setpoint by
this value, a Low
Control Temp
Alarm will oc-
cur. Only applies
if confi gured for
Space or Return
Air Temp Con-
trol, or as Single
Zone VAV.
0
50
Control
Status
CtrlSts
AI: 4
Current
operational
status.
See Control
Status Bits on
page 43.
Control
Tempera-
ture
CtrlTp
AI: 9
Current value of
the control
temperature
sensor.
Cooling
Enabled
ClEnbl
AI: 6
Status that
indicates
mechanical
cooling is
enabled to
operate.
BACnet Properties for the VCB-X Controller
Param-
eter
Name
Object
Description
Limits
Mechani-
cal Cooling
Lockout
MchClLkt
AV: 342
The VCB-X
will Lockout
Mechanical
Cooling when
the Outdoor Air
Temperature
is below this
Setpoint.
-30
100
Mechani-
cal Cooling
Alarm
MchClAlm
BI: 94
Compressor Re-
lays are enabled
but the Supply
Air Temperature
has not fallen
5°F within a
user-adjustable
time period. This
does not apply
for Modulating
Cooling.
Cooling
Setpoint
Mirror
ClSt
AI: 7
Occupied
Cooling Mode
Enable
Setpoint.
Cool
Staging
Window
ClStgWdw
AV: 340
In Cooling
Mode, if the
Supply Air
Temperature
drops below the
Active Supply
Air Cooling
Setpoint minus
this Staging Win-
dow, a Cooling
Stage will be
deactivated after
its Minimum
Run Time.
1
30
Adaptive
Defrost
Interval
Adjust-
ment
AptDfr
AV: 356
Adjustment to
the Heat Pump
Defrost Interval
depending on
whether the
Defrost Mode
lasts 10 minutes
or less than 10
minutes.
0 Min
30
Min
Dewpoint
Setpoint
RhDewpSt
AV:282
On a MUA unit,
if the outdoor
dewpoint rises
above this
setpoint, the unit
will
activate Dehu-
midifi cation.
35
80