Parameter tables, 3 vcm-x wshp tulsa & rne bacnet parameters, Pt-link ii bacnet3 interface 46 – Orion System PT-Link II BACnet3 User Manual
Page 46: Zone

Zone
Zone
7. PARAMETER TABLES
PT-Link II BACnet3 Interface
46
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
Parameter
Name
Object
Description
Limits
Compressor 4
Lockout Alarm
B2LktAlm
BI: 229
Alarm that
indicates
Compressor B2
is locked out.
Low Water
Temperature 1
Alarm
LWT1Alm
BI: 230
Alarm that
indicates water
temperature is
below the
Leaving Water
Safety Setpoint
(Heating only)
for System A.
Low Water
Temperature 2
Alarm
LWT2Alm
BI: 231
Alarm that
indicates water
temperature is
below the
Leaving Water
Safety Setpoint
(Heating only)
for System B
Proof of Water 1
Flow Alarm
POWF1Alm
BI: 232
Alarm that
indicates no
Proof of Water
Flow for System
A (A1/A2)
Proof of Water 2
Flow Alarm
POWF2Alm
BI: 233
Alarm that
indicates no
Proof of Water
Flow for System
B (B1/B2)
Module
Communica-
tions Alarm
ComMAlm
BI: 234
Alarm that
indicates that one
or more Modules
are not
communicating
with the VCM-X
WSHP Control-
ler.
Bad Return Air
Sensor
RaTpAlm
BI: 365
Alarm that
indicates
a failure in the
Return Air Sen-
sor.
Title 24 Econo-
mizer Feedback
T24EcFb
AI: 384
Current position
of feedback from
Economizer
actuator.
7.3 VCM-X WSHP Tulsa & RNE BACnet Parameters
BACnet Properties for VCM-X WSHP (Tulsa)
and RNE Controllers
Parameter
Name
Object
Description
Limits
Title 24
Sensor Alarm
T24TpAlm
BI: 385
Outside Air
or Supply Air
Temperature
Sensor is shorted
or missing.
Title 24 Not
Economizing
When It Should
T24NEWS
BI: 386
Economizer is
enabled but not
following the
desired Econo-
mizer position
commanded.
Title 24 Econo-
mizing When It
Should Not
T24EWISN
BI: 387
Economizer is
not enabled but
the feedback
signal indicates
a position more
open than the
minimum.
Title 24 Damper
Failure
T24DpAlm
BI: 388
Economizer is
enabled but not
within 10% of
desired position
within 150
seconds.
Title 24 Excess
Outdoor Air
T24ExsOA
BI: 389
Economizer
feedback is lost
or Economizer
is not follow-
ing commanded
position.