beautypg.com

Wiring diagrams, Pulser wiring requirements – Gasboy CFN Series Site Controller III User Manual

Page 59

background image

MDE-4298D CFN Series Site Controller III Installation Manual · September 2009

Page 55

Wiring Diagrams

Pump/Remote Dispenser Wiring

Pulser Wiring Requirements

18 AWG wires are required for the installation of a pulser in a separate DC conduit. Although
it is recommended that DC pulser wires be run in a conduit away from AC wires, they can be
combined in the same conduit with AC wires if a UL-listed cable with the following
specifications is used:

Conductor

18 AWG stranded wire. Number of conductors to be determined by the pulser.

Shield

Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage

Drain Wire

Stranded, tinned copper, 20 AWG or larger/or braided shield

Voltage Rating

Maximum operating voltage of 600 V

Environmental

Gas and oil-resistant; suitable for wet or dry locations

Gasboy can supply Belden 1063A (Part Number C09655) which is a UL-listed, 4-conductor
cable that meets the requirements listed above.

Note: Belden 1063A is UL-listed but not CSA-listed.

Wiring Diagrams

This section contains the following wiring diagrams.

Figure 5-9: Single Suction Pump, VR Reset

on

page 56

Figure 5-10: Twin Suction Pump, VR Reset

on

page 57

Figure 5-11: Twin Suction Pump, Single Motor, VR Reset

on

page 58

Figure 5-12: Single Remote Dispenser, VR Reset

on

page 59

Figure 5-13: Twin Remote Dispenser, VR Reset

on

page 60

Figure 5-14: Single Suction Pump, Console, VR Reset

on

page 61

Figure 5-15: Twin Suction Pump, Console, VR Reset

on

page 62

Figure 5-16: Twin Suction Pump, Single Motor, Console, VR Reset

on

page 63

Figure 5-17: Single Remote Dispenser, Console, VR Reset

on

page 64

Figure 5-18: Twin Remote Dispenser, Console, VR Reset

on

page 65

Figure 5-19: Single Suction Pump, Gasboy Reset

on

page 66

Figure 5-20: Twin Suction Pump, Gasboy Reset

on

page 67

Figure 5-21: Twin Suction Pump, Single Motor, Gasboy Reset

on

page 68

Figure 5-22: Single Remote Dispenser, Gasboy Reset

on

page 69

Figure 5-23: Twin Remote Dispenser, Gasboy Reset

on

page 70

Figure 5-24: Single Suction Pump, Console, Gasboy Reset

on

page 71

Figure 5-25: Twin Suction Pump, Console, Gasboy Reset

on

page 72

Figure 5-26: Twin Suction Pump, Single Motor, Console, Gasboy Reset

on

page 73

Figure 5-27: Single Remote Dispenser, Console, Gasboy Reset

on

page 74

Figure 5-28: Twin Remote Dispenser, Console, Gasboy Reset

on

page 75