MDE-4298D CFN Series Site Controller III Installation Manual · September 2009

Page 39

Short Haul Modem (SHM) RS-422

System Components Wiring

Short Haul Modem (SHM) RS-422

A Gasboy SHM and the appropriate interconnect cable must be used when the RS-422
communication mode is being used. It should be used for distances between 100 and
1500 feet. It can be used for distances under 100 feet in place of RS-232 wiring. One SHM is
required at each end of the communication line.

Figure 4-7: SHM Connections

• All wiring must be installed and used in accordance with all building/fire codes, all

Federal, State, and Local codes, National Electrical Code (NFPA 70), NFPA 30, and
Automotive and Marine Service Station (NFPA 30A) codes and regulations. Wiring must
conform to the wiring diagram supplied with the pump/remote dispenser also. Canadian
users must also comply with the Canadian Electrical Code.

Power: The AC power for the SHM should come from the same breaker that supplies the

peripheral device or the system.

Cable: Twisted-pair shielded cable is highly recommended for RS-422 wiring. Although

it is recommended that wires be run in a conduit separate from AC wires, they can be
combined in the same conduit with AC wires if a UL-listed cable with the following
specifications is used.

Conductor

18 AWG stranded wire; 2 twisted-pairs

Shield

Foil-wrapped 100% coverage and/or tinned copper braid 90% coverage

Drain Wire

Stranded, tinned copper, 20 AWG or larger/or braided shield

Voltage Rating

Maximum operating voltage of 600 V

Environmental

Gas and oil-resistant; suitable for wet or dry locations

Gasboy can supply Belden 1063A (Part Number C09655) which is a UL-listed,

4-conductor cable that meets the requirements listed above.

Note:Belden 1063A is UL-listed but not CSA-listed.

If a cable with a voltage rating of less than 600 V is used, it must be installed in a conduit
away from all AC wires.