Location – Gasboy CFN Series Site Controller III User Manual

Page 14

background image

System Layout

SC III

Page 10 MDE-4298D CFN Series Site Controller III Installation Manual · September 2009

In addition to SC ports, Personal Computer (PC) peripherals (monitor, mouse, and so on) are
connected as per the manufacturer’s instructions.

Figure 3-1

shows SC ports as installed on a

representative PC (your actual PC layout may differ).

Location

The SC III should be located in an office-like environment and in an area protected from direct
contact with the weather. Do not install the SC unit in a hazardous location. The unit is
designed for an operating temperature range of 40 °F to 95 °F with a relative humidity of 20%
to 80% (non-condensing). Placing the SC unit in a dirty environment may cause premature
failures. The RS-485 junction box must be located within 8 feet of the SC unit. The RS-485
junction box must be grounded as specified in

“Power Requirements”

on

page 32

. The SC unit

should not be placed on top of any other components and no other equipment should be placed
on top of the SC unit.

Figure 3-1: SC III

Notes:
1. Location of PC connectors may differ.
2. Ethernet Port and the USB may be disabled depending

on Operating System (OS) and PC settings.

Power Switch

PS/2 Mouse

PS/2 Keyboard

COM1/Serial1

Monitor

Printer

USB 1/2

Ethernet (Refer Note 2)

USB 3/4 (Refer Note 2)

Speaker

COM2/Serial 2

COM Ports 3-6

Power In

Port 1 Local RS-232

Port 6 RS-232

Port 5 RS-232

Port 4 RS-232

Loop1 Island RS-485 Port

Loop2 Island RS-485 Port
Factory Set to Two-wire for Tokheim

Loop3 POS High Speed RS-485 Port

Port 3 Unused