System Components Wiring

Communication Requirements

Page 34 MDE-4298D CFN Series Site Controller III Installation Manual · September 2009

RS-485 Modular Cable: The RS-485 modular cables required are supplied with the

system. These cables are not compatible with standard phone cables that are obtained from
other sources.

Gasboy-supplied cables are 8 feet long. If you need to connect a CFN component with a
modular connector (console) that is more than 8 feet from the system, you must use an

RS-485 junction box to connect the device to the RS-485 communication wiring.

Connections: Refer to

“System Components Wiring Diagram”

on

page 35

for proper

connection of the RS-485 field wiring to the CFN system components.

RS-232

RS-232 wiring can be used for communication between the CFN SC and EIA RS-232
compatible peripheral devices (printer, modem, and so on). The remote end of the wiring can
be terminated with either an RS-232D connector or a Gasboy termination box. You must
follow these installation requirements when installing the CFN RS-232 communication lines:

• All peripheral equipment connected to the RS-232 ports must be listed, have an EIA

standard RS-232 communication protocol and should not be installed in a hazardous
location.

Distance: The following distances must be adhered to when installing the RS-232

communication lines:
- 1 - 100 feet: RS-232 can be directly connected to a peripheral device.
- 101 - 1500 feet: An RS-422 Cable and a Gasboy SHM are required (refer to

“Short Haul

Modem (SHM) RS-422”

on

page 39

).

Conduit: All direct connect RS-232 Cables over 15 feet must be in a metal conduit away

from any AC wires. For conduit requirements of SHMs, see the installation sheet that
applies to the device being used.

Cables: RS-232 Cables can be purchased from Gasboy. The type of cable required will

vary according to the devices it connects.

Connection

Cable Type

Gasboy Part Number

Port 1, 4, 5, and 6 to modem

MiniDIN to 25DB

C05995

Port 1, 4, 5, and 6 to terminal

MindDIN to 25DB

C05994

* All electronic pumps and controls must be installed according to the manufacturer’s specifications.

Figure 4-1: RS-232 1:1 Cable (Part Number Q13240-09 - 6-feet M/F)

DB 25
Male

DB 9
Female

13

25

1

14

5

1

9

6

RS-422

For guidelines and restrictions on RS-422 wiring, refer to

“Short Haul Modem (SHM) RS-422”

on

page 39

.

Two-wire Current Loop

For guidelines and restrictions on the Two-wire Current Loop used for ICR2, refer to

MDE-2713 Universal Distribution Box Installation manual.