XPA200-7984-I-OPT1, X-Band SSPA

Remote Control

Remote Control

XPA200-7984-I-OPT1, Rev.2

5-15

5.8.3.8 Packed Configuration Status

Configuration Status: _'cr'

Confirmation:

>DEV/PACRCS_aabcdeefg'cr''lf']

where:

aa = # of 0.25 dB steps in HEX above 0dB (0to120)

b = 1 if Amplifier ON, 0 if OFF

c = 1 if Tx ON, 0 if OFF

d = 1 if unit ONLINE, 0 if OFFLINE

ee = SSPA number = BU,01 or 02 (if e = 0, ff = 00)

f = A if Auto Mode, M if Manual Mode

g = 1 if Auto Recovery enabled, else 0

5.8.3.9 Packed Maintenance Status

Packed Maitenance Status: _'cr'

Confirmation:

>DEV/PACRMS_

aabbccddeeffgghhhiiijjj'cr''lf']

where:

aa = +28 supply, 100mV per count above 10.0V in Hex

bb = +12 supply scaled 100mV per count in Hex

cc = -12 supply scaled 100mV per count in Hex

dd = +5 supply scaled 100mV per count in Hex

ee = -5 supply scaled -100mV per count in Hex

ff = +10 supply #1 scaled 100mV per count in Hex

gg = +10 supply #2 scaled 100mV per count in Hex

hhh = Signed temperature in degrees C (-10 to +95)

iii = RF forward pwr, .1 dBm steps above 32.0 dBm in

Hex

jjj = RF reverse pwr, .1 dBm steps above 25.0 dBm in

Hex

5.8.3.10 Packed FET Status

Packed FET Status:

_'cr'

Confirmation:

>DEV/PACRFS_

aabbccddeeff. . rrss'cr''lf']

where:

aa = FET1 current in Hex, formula: FET1 = (aa * 3)mAmps

bb = FET2 current in Hex, scaled 100mA per count

cc = FET3 current in Hex, scaled 100mA per count

dd = FET4 current in Hex, scaled 100mA per count

ee = FET5 current in Hex, scaled 100mA per count

ff = FET6 current in Hex, scaled 100mA per count

gg = FET7 current in Hex, scaled 100mA per count