beautypg.com

Pilz PSSnet SHL 8T MRP User Manual

Page 125

background image

Diagnosis

PSSnet SHL - Web- based Interface

Pilz GmbH & Co. KG, Felix- Wankel Str. 2, 73760 Ostfildern

7.5 Device Status

125

The events which can be selected are:

…

Select "Generate Trap" in the "Trap configuration" field to activate the
sending of a trap if the device state changes.

Note: With non-redundant voltage supply, the device reports the absence of
a supply voltage. You can prevent this message by feeding the supply volt-
age over both inputs, or by switching off the monitoring

(see on page

144

„Signal contact“)

.

Name

Meaning

Power supply ...

Monitor/ignore supply voltage(s).

Temperature

Monitor/ignore temperature thresholds set

(see on page

16

„System“)

for

temperatures that are too high/too low

Module removal

Monitor/ignore the removal of a module (for modular devices).

SCA removal

Monitor/ignore the removal of the SCA.

Connection error

Monitor/ignore the defective link status of at least one port.
The reporting of the link status can be masked for each port by the
management

(see on page

26 „Port configuration“)

. Link status is not

monitored in the state on delivery.

HIPER-Ring

Monitor/ignore the discard of the existing redundancy (in Ring Manager
mode).
State on delivery: ring redundancy is not monitored.

Ring/Network Cou-
pling

Monitor/ignore the failure of the redundancy.
State on delivery: ring redundancy is not monitored.
The following conditions are also reported by the device in standby
mode:
– Defective link status of the control line
– Partner device is in standby mode.

Fan

Monitor/ignore fan function (for devices with fan).

Table 44: Device Status

This manual is related to the following products: