Property Description
The input data point for this Alarm Generator. The data point must be
referenced by its
Each time this data point is updated, its value will be compared to the
value of the compare data point using the comparison function defined by
the
True, an alarm will be generated.
The
AL_ALM_CONDITION when an alarm is generated, unless the
this case, the status will be updated to any of four alarm statuses, based on
the offset limit that caused the alarm. For more information on this, see
Hysteresis Levels and Offset Limits on page 7-13.
You can register the input data point with the Alarm Notifier application
to generate alarm notifications and e-mail messages each time it is
updated to an alarm status. For more information on this, see Alarm
Notifier on page 8-1.
The compare data point for this Alarm Generator. The data point must be
referenced by the
and must use the same format type as the input data point. The value of
this data point will be compared to the value of the input data point each
time either point is updated.
Use an NVC data point as the compare data point if you want your alarm
generator to generate alarms based on a constant value configured through
software, as opposed to a live value taken from the network.