beautypg.com

1 input data points – Echelon i.LON 100 e2 Internet Server User Manual

Page 116

background image

i.

LON 100 Internet Server Programmer’s Reference

Property Description

If the input data point is updated and matches the conditions defined by

any of the active alarm condition sets, it is considered an active alarm. In

this case, the Alarm Notifier will use its active destinations. You can
create as many active alarm condition sets as you want per Alarm

Notifier.
The active alarm condition sets for an Alarm Notifier are signified by a
list of elements. For a description of the properties that

must be defined within each element, see Active and
Passive Alarm Condition Sets
on page 8-15.

If the input data point is updated and matches the conditions defined by
any of the passive alarm condition sets, it is considered a passive alarm.

In this case, the Alarm Notifier will use its passive destinations. You can

create as many passive alarm condition sets as you want per Alarm
Notifier.
The passive alarm condition sets for an Alarm Notifier are signified by a
list of elements. For a description of the properties that

must be defined within each element, see Active and

Passive Alarm Condition Sets on page 8-15.

Each element defines a group of active and passive alarm

destinations the Alarm Notifier will use. The active destinations are
signified by a list of child elements within the

element. The passive destinations are signified by a list of
child elements within the element. For a

description of the properties that must be defined within each of these

child elements, see Active and Passive Alarm Destinations on page 8-16.

Each element also contains 2 global elements: its index

number (UCPTindex), and its enable data point (UCPTdestEnable). The

property is optional. You can reference a
SNVT_Switch data point by its name (UCPTpointName) here. The

will then be enabled when that data point is set to 100.0 1,
or disabled if that data point is set to 0.0 0. You could set this data point

with a L

ON

W

ORKS

switch, or with the Event Scheduler application.

This allows you to enable or disable an Alarm Notifier’s destination sets
under different circumstances.

8.2.1.2.1 Input Data Points

The following table describes the properties that you must define within each

element. As described in the previous section, each element defines an input data

point for the Alarm Notifier. Each time any of the input data points are updated, the Alarm
Notifier will check if it has reached an alarm condition.
If an input data point is updated and meets an active or passive alarm condition, then an
alarm notification will be loggeed, and the applicable passive or active alarm destinations

will be used.

8-10