Q. How much electrical power is required for a BTH water heater?

A. The BTH models draw approximately 5.0 Amps Max.

Q. When should BTH’s be delimed?

A. Many variables affect the lime build up process including:

Water temperature — the amount of lime accumulation during the same period of time will be

nearly 2 times great if water is stored at 140 degrees F than at 120 degrees F. A 180° setting
may accumulate seven times more lime — in a period of time — than at 140° setting.

Volume of water— the more gallons flowing through the BTH, the more rapid the

accumulation.

Hardness — the harder the water the quicker lime build up occurs. 1 to 3.5 grains per gallons

is “soft”, 3.5 to 7 grains per gallon is “moderate”, 7 to 10.5 grains per gallons is “hard” and

10.5+ grains per gallon is “very hard”. (An aspirin is about 5 grains. One grain is equal to 17.1

parts per million.)

A. Deliming should be done when a slight rumbling or popping sound is detected when the main

burner is on. Check for accumulation through the clean-out opening.

Q. What effect will lime build-up have on the BTH water heater?

A. One eighth inch of scale buildup on the heat exchanger may reduce efficiency as much as

22%: a % inch buildup, as much as 38%.

Less efficient heat transfer means more heat exchanger expansion/contraction stress and pre­
mature leakage.
Because the heat transfer to the water is made through a (relatively) small diameter, coil type

exchanger tube, expansion and contraction as well as the shape of the exchanger greatly

reduces buildup on the heat transfer surface. The bottom of the tank should be checked for

dislodged accumulation.

Q. Anode rods (4) provide additional protection against corrosion. When should these be

replaced?

A. When large gauges or pits appear in the anodes, replace them.

Q. How often should the anodes be inspected?

A. Approximately every six months.