MAKE-UP AIR

Direct Communication

Each opening shall
have a free area not
less than:

1 square inch per

4000 BTUH total input
all appliances within
the enclosure

Inlake

Air

12

Opening

Iniciko

Air Opening

L

12

A fresh supply of make-up air for combustion can be supplied to the heater through make-up air

openings, which directly communicate with the out of doors. Two openings are required — one

within 12 inches of the top of the enclosure and one within 12 inches of the bottom of the enclosure.

Each opening shall have a free area of not less than 1 square inch per 4000 BTUH of the total input

of all appliances within the enclosure.

The lower opening is primarily providing combustion air. The upper opening is providing vent dilu­
tion air and acts as a relief opening for flue gases should the vent become obstructed or a down
draft condition occur.

MAKE-UP AIR

Vertical Ducts

Air Intake Ducts

Each opening shall
have a free area not
less than:

12”

1 square inch per

4000 BTUH total input
all appliances within
the enclosure

12”

Often it is more practical to install vertical make-up air ducts to the outdoors. Again, two openings
are required — within 12 inches (30 cm) of the top of the enclosure and one within 12 inches (30
cm) of the bottom of the enclosure. Each opening shall have a free area of not less than 1 square
inch per 4000 BTUH of the total input of all appliances within the enclosure.