BTH S E R V I C E H A N D B O O K

I N S T A L L A T I O N

INSTALLATION

CLEARANCES

CEILING

‘1.5

l_gpj

WALL

REAR WALL

.ÜT

. 0" ,

LEFT

RIGHT
WALL

RIGHT

WALL

FRONT VIEW

*For removal of top cover

This portion of the handbook will review
often overlooked installation require­

ments. The installation manual covers

these items in detail. BTH water heaters
are approved for installation on com­

bustible flooring. The minimum clear­

ance to combustibles or non­
combustibles is 0 inches from the sides

wa

L

i

I

and rear, 0 inches from vent piping, and

1.5 inches from the top cover. A 24 inch

top

view

clearance for all serviceable parts is

recommended. Clearances may vary
between BTH models. See installation
manual or the label on the heater for

your specific model.

GAS REQUIREMENTS

N O T E :

Pressure without capacity will result in lockout. Follow the piping guidelines in the

installation manual. The supply gas pressure is normally measured at the dirt leg or at the inlet gas
pressure tap on the gas valve. This reading must be measured with ‘flowing’ gas.

The manifold gas pressure is measured at the manifold pressure tap on the gas valve when the
gas is flowing. The gas valves used on all BTH water heaters are 24 VAC combination step open­

ing gas valves. They incorporate the main valve and pressure regulator into one body.

REGULATED GAS SUPPLY LINE

PRESSURE REGULATOR

ADJUSTMENT

(COVER

screw

'

INLET PRESSURE

TAP

GAS INLET

GAS VALVE ON/OFF

TH & TR TERMINALS
(MAIN VALVE)

VIANIFOLD

PRESSURE TAP

GAS OUTLET

GAS SUPPLY SPECIFICATIONS

BTH 120 & 250

BTH 150 & 199

BTH 120, 150 &

199

NATURAL GAS

NATURAL GAS

PROPANE GAS

Max. Gas Supply Pressure Inches W.C.

12.0 (3 kPa)

12.0 (3 kPa)

14.0(3.45 kPa)

Nominal Gas Supply Pressure Inches W.C.

7.0 (1.75 kPa)

7.0 (1.75 kPa)

11.0 (2.74 kPa)

Minimal Gas Supply Pressure Inches W.C.

5.5 (1.37 kPa)

4.5 (1.12 kPa)

11.0 (2.74 kPa)

Manifold Pressure Inches W.C.

4.0 (1 kPa)

3.5 (0.8 kPa)

10.0 (2.5 kPa)

A. O. Smith Water Products Co.
Ashland City, Tennessee © 2004

Technical Training Department

TC-044 Revision 6