Table 3 - Electrical Data for 06D Compressor Units and
07D Water-Cooled Condensing Units
06D
07D
Full
Locked
Overload
Fusetron
Min Branch
Max Wire
Reference
Compressor
Condensing
Volt/Phase
Load
Rotor
Trip
Size
Max
Circuit Wire
Length
Old
Unit
Unit
Cycle
(amps)
(amps)
(amps)
(amps)
Kw
Size (AWG)
(ft)*
Number
A102
208/3/60
7.9
48.5
11.0
12.0
2.8
14
49
6D21
230/1/60
11.2
50.0
15.6
17.5
2.8
14
29
230/3/60
6.8
43.0
9.5
12.0
2.8
14
63
460/3/60
3.5
22.5
4.8
5.6
2.8
14
249
230/3/50
5.8
35.8
8.0
10.0
2.35
14
74
400/3/50
3.5
21.5
4.8
5.6
2.35
14
216
A808
A203
208/3/60
11.8
63.5
16.5
20.0
3.8
14
32
6D28
230/1/60
15.8
70.0
22.0
25.0
3.8
12
34
230/3/60
10.3
57.5
14.4
17.5
3.8
14
41
460/3/60
5.2
28.8
7.2
9.0
3.8
14
164
230/3/50
8.6
47.8
12.0
15.0
3.17
14
50
400/3/50
5.2
27.5
7.2
9.0
3.17
14
143
A103
208/3/60
12.2
63.5
17.0
20.0
4.1
14
31
6D40
230/1/60
16.1
70.0
22.5
25.0
4.1
12
33
230/3/60
10.6
57.5
14.8
17.5
4.1
14
35
460/3/60
5.3
28.8
7.4
9.0
4.1
14
161
230/3/50
8.9
47.7
12.4
15.0
3.42
14
36
400/3/50
5.3
27.5
7.4
9.0
3.42
14
140
A718
A106
208/3/60
19.3
95.0
27.0
30.0
6.6
10
50
6D47
230/1/60
25.0
100.0
35.0
40.0
6.6
10
32
230/3/60
16.8
86.0
23.5
30.0
6.6
10
63
460/3/60
8.5
43.0
11.8
15.0
6.6
14
100
230/3/50
14.0
72.0
19.5
25.0
5.5
12
48
400/3/50
8.5
41.0
11.8
15.0
5.5
14
87
A818
A208
208/3/60
35.0
137.0
48.8
60.0
10.8
6
63
6D48
230/3/60
31.5
124.0
44.0
50.0
10.8
8
53
460/3/60
15.8
62.0
22.0
25.0
10.8
12
85
230/3/50
26.2
103.0
36.7
40.0
9.0
8
64
400/3/50
15.8
59.0
22.0
25.0
9.0
12
74
*210
208/3/60
36.0
137.0
48.8
60.0
10.8
6
63
6D67
230/3/60
31.5
124.0
44.0
50.0
10.8
8
53
460/3/60
15.8
62.0
22.0
25.0
10.8
12
85
230/3/50
26.2
103.0
36.7
40.0
9.0
8
64
400/3/50
15.8
59.0
22.0
25.0
9.0
12
75
¿824
208/3/60
44.0
170.0
61.5
70.0
14.1
6
41
6D68
230/3/60
39.7
153.0
55.5
70.0
14.1
6
63
460/3/60
19.9
77.0
27.8
35.0
14.1
10
107
230/3/50
33.0
128.0
46.2
50.0
11.7
6
76
400/3/50
19.9
74.0 •
27,8
35.0
11,7
10
85
*337
¿112
208/3/60
49.3
191.0
69.0
80.0
15.9
4
69
6D73
230/3/60
44.3
172.0
62.0
70.0
15.9
6
57
460/3/60
22.2
86.0
31.0
35.0
15.9
10
96
230/3/50
37.2
143.0
52.0
60.0
13.2
6
67
400/3/50
22.2
83.0
31.0
35.0
13.2
10
83
¿537
¿215
208/3/60
55.7
266.0
78.0
90.0
18.9
4
61
6D75
230/3/60
50.0
240.0
70.0
80.0
18.9
4
75
460/3/60
25.0
120.0
35.0
40.0
18.9
8
131
230/3/50
41.5
200.0
58.0
70.0
15.7
6
60
400/3/50
25.0
115.0
35.0
40.0
15.7
8
115
*Wlre sizes are based on minimum wire size needed to
comply with Notional Electric Code for TW Type Wire.
Maximum wire length is based on a 1% voltage drop in the
branch circuit. Where up to
3
%
voltage drop is acceptable,
maximum wire lengths can be multiplied by 3.
14